Electric power system
The whole of electrotechnical installations and networks including all necessary additional devices for the generation, transmission and use of electric power within one regional unit,
Electrotechnical installation (or plant)
The whole of equipment required for proper functioning of the complete technological unit.
Electrotechnical network (or electric mains)
A system of interconnected electric lines of the same rated voltage for the transmission and distribution of electric power.
Supergrids (extra-high voltage systems)
(transmission
function)
for power supply to larger areas with transmission voltages of 110
kV, 220 kV and 380 kV.
Medium-voltage systems
(distribution function) for
power supply to smaller areas (towns, parts of towns, industrial plants, etc.)
with transmission voltages of 1 to 30 kV.
Low-voltage systems (supply function) for power supply to the majority of consumers (electric household appliances and motors of low and medium capacity) with transmission voltages of up to 1 kV.
Open systems
have a single feeding point.
Closed systems
have two feeding points which makes
the network more fail-safe.
Figure 7. Various types of networks
as integral parts of the electric power transmission system - (1) supergrids
(extra-high voltage systems (2) medium-voltage system (3) low-voltage systems -
1 mesh-operated network, 2 medium-voltage ring-operated network, 3 low-voltage
distribution network (closed), 4 open network (multiple lump-loading), 5 star
network, 6 feeding
Figure 8. Example of interconnected
national networks - 1 transmission levels, 2 distribution levels, 3
international networks, - (1) power station, (2) heat-generating station, (3)
industrial power station, (4) pumped storage power station
Table 2 Open and closed systems (networks)
Type and circuit | |
Advantages and disadvantages |
Examples of application |
Open systems with |
end-loaded lines |
simple circuit, clear arrangement, very simple protective system, very easy planning, good utilization, low costs, poor operational reliability, poor voltage maintenance, high losses |
small industrial plants and local networks of small extent |
|
multiple lump-loaded lines |
|
|
|
branched lump-loaded lines |
|
lighting installations |
|
| | |
Closed systems with |
lines with double feeding |
simple circuit |
local networks for long-distance settlements, extended factory halls |
Closed system of |
ring layout |
clear arrangement |
factory plants, medium-voltage distribution networks, higher-level supergrids |
|
star layout |
better voltage maintenance, less losses, easy planning, better operational reliability, poor utilization, acceptable costs, sophisticated protective system |
low-voltage distribution networks in big industrial plants |
|
meshed layout |
very good operational reliability, very good voltage maintenance, low losses, very good utilization, less simple circuit, less clear arrangement, very sophisticated protective system, less easy planning, acceptable costs |
local networks for bigger and large towns, low-voltage networks for big companies |
The designation of networks and conductors is internationally coded to IEC 445.
The code letters used have the following meaning:
T terre (French) (earth)
I insulation
N neutral wire
C combined
S separated
P protection
E earth
TN-networks
Networks where one point of the network, i.e. one point of the service circuit, is directly earthed (T) and the casings of the equipment or installations are electrically connected with such point through a protective conductor (N). They apply the protective measures of connection to neutral or protective earthing with fault current return through metallic conductors (water pipes, cable sheathings).
- TN-C-network
PEN protective conductor with function of
neutral wire.
Figure 9. TN-C-network
- TN-S-network
PE protective conductor carrying no operating
current.
Figure 10. TN-S-network
- TN-C-S-network
PE protective conductor carrying no
operating current.
Figure 11. TN-C-S-network
TT-networks
Networks where one point of the network is directly earthed (1) and the casings of the equipment or installations, irrespective of the existence of any neutral wire, are connected with earth leads which are not electrically connected to the earthed network point (T). Such networks, which are internationally called TT-networks, apply protective earthing (single earthing) using FI or FU protective circuits.
TT-network
Figure 12. TT-network
IT-networks
Networks where no point of the network is directly earthed (I) but the casings of the equipment or installations are directly earthed (T). Such networks apply the protective conductor system, protective earthing, FI and FU protective circuits.
IT-network
Figure 13.
IT-network
The amount of voltage is decisive for the thickness of the insulation material (wire insulation) or the size of the distance of active conductors between each other and the earth. Economically this means the use of expensive or less expensive insulation material and, with respect to overhead lines, additionally occupation of ecologically important land. High-voltage overhead lines also involve overhead construction problems. Depending on the climatic zones, loads due to wind and ice, for example, are material-intensive design factors.
The variety of the individual levels shall be demonstrated by means of an example of an installation
Figure 14. Example of possible
voltage levels - 1 generator, 2 generator transformer, 3 substation transformer,
4 distribution transformer, 5 consumers, 6 voltages in kV
To enable efficient transmission of high powers over large distance, the transmission voltages have become higher and higher in the course of technological development.
Figure 15. Development of
transmission voltages worldwide - 1 high-voltage three-phase transmission, 2
high-voltage D.C.
transmission
Having dealt with the effects of the voltage on the physical dimensions of all electrotechnical transmission elements, we now consider the effects of the electric current:
There are three objective factors of influence on the dimensioning.
The operating current is important for normal operation which may be of continuous, short-time or intermittent type.
Continuous operation
Continuous operation means uninterrupted loading of all transmission elements by current of almost constant intensity which, depending on the current density, results in heating of the active conductors. That means that all materials and auxiliary materials (insulation) as well as components, which are in direct contact with the active conductor, absorb heat. The consequences are expansion and aging effects on busbars, metal-clad cables, wire insulations etc.
Short-time operation/intermittent operation
Short-time operation/intermittent operation mean that, after periods of heating, all transmission elements undergo periods of cooling. This may be aimed at maximum thermal peak-load on the one hand or at thermal load below the limit load on the other hand. It depends on the components to be used.
Faults normally involve extreme loads for all components, depending on the design of the installation in terms of protection:
- Instantaneous short-circuit current
The so-called instantaneous or asymmetric short-circuit current involves high electrodynamic loads for the installation parts immediately on its occurence. The intensive magnetic fields generated as a consequence of such current can physically destroy busbar installations, current transformer heads (insulator-type transformer), switching devices etc. Conductor elements of overhead lines may also be affected.
- Sustained short-circuit current
The sustained short-circuit current occuring after the instantaneous short-circuit current has several times the intensity of the operating current and, with a time lag after the short- circuit, results in heavy or extreme heating of all components in the fault circuit. Mostly such current destroys the installation parts unless this is prevented by adequate protective measures.
The thermal effects of the environment are important for the dimensioning of the installation with respect to the cross sections of the transmission elements and to the protective elements to be used. High ambient temperatures physically call for larger cross sections and low ambient temperatures permit smaller cross sections than normally specified for the operating current. Mutual heating is taken into account in installation engineering by providing for adequate distances of busbars, stranded conductors, lines and cables between each other and between components and for air circulation.
Outdoor plant/installation
Installation exposed to
weather conditions without protection (see outdoor).
Open-type plant/installation
Installation with
equipment not fully protected against accidental contact.
Outdoor(s)
Limited area in the open air featuring the
same temperature and air humidity according to the local climate.
Assembly unit
A combination of several components or
devices forming a functional unit.
Component
A single part that can only work in
connection with other components.
Subassembly/module
Locally combined group of
components which can function independently. Subassembly (in the context of a
project) is a self-contained part of a plant/installation as defined from
shipping and installation aspects.
Modular component/module
A component which, because of
its specific modular design, can be assembled with other similar modular
components into a consistent whole.
(Component) part
A constructionally and electrically
self-contained member of a part of an installation.
Enclosed
Equipment and plants/installations which are
protected against environmental influences.
Protected outdoor installation/plant
Outdoor
installation which is protected against rainfall up to an angle of incidence of
30 degrees to the perpendicular.
Main distribution (system)
First distribution system
after power feeding.
Information unit
The information unit of an
installation or section or part of an installation comprises its locally
functionally combined equipment for the generation, transmission, processing and
reception of information, even though this is implemented according to the rules
of heavy-current engineering.
Indoor installation/plant
Installation inside rooms or
buildings.
Indoor(s)
Room in buildings which is free from effects
of weather conditions
Mesh network
Closed network system consisting of
crossing lines which are interconnected and fused at the crossing points. The
crossing points are called nodal points, the closed sections between
the nodal points a mesh and each part of the line mesh
line.
Nodal point of a network
A point in the electric
energy distribution system where more than two circuits (lines) can be
interconnected.
Potential equalization
Electrically conductive
connection between electrically inactive parts, such as water, gas and heater
pipes, steel structures, metallic cable sheathings, foundation earth leads and
protective conductors. This measure prevents a potential difference (voltage)
between such parts.
Figure 16. Example of central
potential equalization - 1 foundation earthing electrode, 2 heating tube system,
3 drinking water pipe, 4 gas distribution pipe, 5 house connection box, 6
customers meter. 7 potential equalization line (connection point
optional), 8 potential equalization bar (if necessary), 9 water meter
(conductively bridged, if the meter is built into a metallic pipe system), 10
structural design
Primary system
It serves the purpose of directly distributing the electric energy and includes all components directly involved in the transmission of electric energy.
(Main) busbar
A conductor - bar or rope - to which
several conductors or lines are connected.
Busbar section
A portion of busbars or busbar
systems.
Each section comprises only one part of the switchboard sections.
Busbar system
Busbars with connected switchboard
sections.
Figure 17. Double busbar system - I
system 1, II system 2
Busbar coupling
Conductive connection between busbar
sections.
Figure 18. Longitudinal busbar
coupling - I, II, III busbar sections
Switching plant
Distribution system with switching devices which make it possible to electrically connect and disconnect the outgoing main lines with/from the busbar.
Switchboard section
Local combination of the elements
belonging to one branch.
Secondary system
It includes all facilities which are
necessary for the protection, control, monitoring, measuring and metering but
are not directly involved in the transmission of electric energy,
Station
Room or part of a building housing one or more
electrotechnical installations or parts of installations and their service
facilities for the purpose of distribution and conversion of electric energy.
Conversion
Change of the nominal value of physical
quantities which are characteristic of the form of electric energy. Conversion
includes transformation, frequency changing, rectification and inversion.
Subsidiary distributing system
Distribution system
following the main distribution system.
Distribution plant
Electrotechnical installation
including accessories, such as actuators, transformers, measuring devices etc.,
the main purpose of which is to distribute electric energy to several outgoing
lines.
Cubicle (cell)
is a construction of suitable material
which stands on the floor and has a degree of protection at least at one side
but not at all
sides.
Lines
They serve the purpose of transmission and
distribution of electric energy in general and of power supply and information
trans-mision of any kind in particular. They are produced as bare (plain) and
insulated types.
Cables
They have the same functions of energy
transmission and distribution. Their particular construction permits their
laying in the media air, soil and water under various external and internal
conditions (mechanical, chemical, physical and electrotechnical).
System earthing and protective earthing wires
They
include all conductors which carry off the electric energy to the earth in the
event of fault. They have the potential of the earth. Since they have to be in
direct contact with the soil, they are not insulated but have a high degree of
protection against corrosion.
Types of laying
- Fixed laying
is a type of laying where the lines cannot change their position after installation (fixed with clips etc.)- Movable laying
is a type of laying allowing the line to be frequently moved to another place (relocation of the equipment connected).
Line resistances
Figure 19. Equivalent connection
diagram of a line - RLeit. line resistance, RIso
insulation resistance, XL inductive reactance (inductance),
XC capacitative reactacne (capacitance), Z consumer
- Ohmic line resistance RLeit
It depends on the length, material, cross section and temperature:
The conductor cross-section is to be selected so as not to exceed the admissible voltage and conduction loss:
- Insulation resistance RIso
It depends on the type of insulation, A general rule for cables
and lines is
The insulation resistance is reduced by dirty surfaces, cracks in the insulation material, increasing tensional load and aging.
- Inductive reactance (inductance) XL
It depends on the line inductance and on the frequency:
The inductance per conductor depends on the length of the line l, the conductor distance a and the conductor radius r. It is calculated as follows:
L |
1 |
a |
r |
H |
km |
mm |
mm |
If it is a line with return line, the total inductance of the line is to be calculated using 2.1 for the length. Because of the small conductor distance a of cables, the inductive reactance of cables is considerably lower than that of overhead lines.
Examples:
|
|
|
|
- Capacitive reactance (capacitance) XC
Capacitive charges occur between conductor and conductor and between conductor and earth.
Figure 20. Equivalent connection
diagram of the capacitances of - a three-phase overhead line, CL
conductor-conductor capacitance, CE conductor-earth capacitance
The mutual capacitance of a three-phase overhead line is calculated as follows:
CB =CE + 3 CL
CB= mutual capacitance
CE = conductor-earth capacitance
CL = conductor-conductor capacitance
Charge current of the three-phase line
The admissible values of capacitance and reactance are
Table 3 Influence of circuit elements on the behaviour of lines with respect to different types of voltage and current
Elements |
Low voltage |
Medium and high voltage |
Direct current |
Three-phase current |
Line resistance |
heating UV, PV |
heating UV, PV |
heating UV, PV |
heating UV , PV |
Insulation resistance |
insulation and corona losses are low |
insulation and corona losses increase with increasing voltage, therefore from 110 1<V bundle conductors for overhead lines |
low corona losses |
insulation between several conductors to be considered, e.g. in multi-conductor cables |
Line inductance |
self-inductance effects in the event of switching operations, little inductive phase shift since short line length |
self-inductance effects in the event of load variations, inductive phase shift increases with increasing line length |
self-inductance effects only when switching on and off |
with 2 three-phase systems and operating currents flowing in opposite directions the self-inductance effects are compensated |
Line capacitance |
low |
medium to high |
capacitance increases with increasing line length and voltage |
line capacitance depends on distance between each of the three conductors, on the insulation and screening |
Bare (plain) lines
Bare lines are non-insulated conductors installed on insulating bodies (insulators), outside the area of contact on poles, behind protective grids or inside casings. As earth leads, bare lines are layed in the soil and in the area of contact.
- Bars (rails)
Solid, non-insulated conductors which, because of their shape or cross section, are highly resistant to deformation. They may be marked by colour codes.
Table 4 Bar (rail) sections and section moduli
No. Section |
Position of conductor bars to each other |
Section moduli |
1 flat |
|
high compared to 2 |
2 flat |
|
low compared to 1 |
3 tubular |
|
very high compared to 4 |
4 round |
|
low compared to 3 and 1 |
5 channel |
|
very high compared to 1 to 4 |
The bars are connected by welded or screwed connections.
They are held by line carriers on porcelain insulators or without carriers on thermoset plastic insulators or in hard paper fans.
Figure 21. Pin-type (rigid-type)
insulator - 1 support, 2 bar carrier for two busbars (laid on edge)
Table 5 Hard paper boards for fixing of busbards
Designation |
Construction |
Comments |
Hard paper fan |
|
easy mounting |
Hard paper fan with end strip |
|
better hold compared to simple fan |
Hard paper board with recesses |
|
to be used where high bending stresses may occur (short circuit) |
- Busbars
Busbars are bars or ropes to which several conductors or lines for current supply or derivation are connected. They are selected according to the current load (thermal load) from tables. Painted busbars can resist higher loads because the paint enables better dissipation of heat. The admissible D.C. load is higher than the A.C. load. Due to the skin effect of A.C. the cross section is not fully utilized. Therefore, pipe sections etc. are used in high-voltage installations. In order to avoid the accumulated temperature (ambient temperature V.. plus conductor temperature V,) to be exceeded, the admissible load current is to be reduced (load reduction) in the event of a higher ambient temperature. This can also be influenced by the way of laying.
Table 6 Cooling at flat section
Way of laying |
Use |
Cooling |
On edge, horizontal |
busbar current bar outlet |
good |
On edge, vertical |
busbar |
good |
Flat, horizontal |
current bar |
very bad |
Flat, vertical |
outlet |
good |
Load because of temperature changes results in displacement of the busbars. Such temperature difference, which may be caused by varying heating effect of the current (alternating load) and by varying ambient temperature of busbars, results in change of length. Busbars are, therefore, fixed in line carriers which permit sliding and/or expansion joints are included in the course of the line. The slide supports and expansion joints make the expansion forces ineffective.
Figure 22. Diagram of busbar laying
- 1 rigid support, 2 slide support, 3 expansion joint
Figure 23. Expansion joint - 1
expandable portion of a multitude of thin strips, 2 connection piece
Loads by heavy currents, such as in the event of short circuit, generate a heavy magnetic field around the conductor. Heavy forces may occur between the fields. Their effect depends on the instantaneous short-circuit current, supporting point distance, conductor section, type of laying and conductor distance.
- Current bars
Current bars are rigid conductors for the transmission of electric energy to portable devices through current collectors. They are used as series line in low-voltage and high-voltage installations. The main materials are half-hard rolled copper or aluminium.
Example:
Figure
- Earth leads
Earth leads are bare conductors lying in the soil with a firm an conductive connection with the soil.
The main materials for protective earthing and system earthing lines are:
· hot galvanized or copper clad strip steel or round steel with a minimum cross section of 50 mm,
· aluminium sections or rope with a minimum section of 35 mm,
· copper sections or rope with a minimum cross section of 16 mm,
· steel rope with a cross section of 120 mm ²
Table 7 Customary minimum cross sections of earth leads
Type of earth lead |
Semi-finished products |
Minimum cross sections/dimensions |
Customary size |
Strip earth conductors |
strip steel |
100 mm² min. thickness: 3 mm |
30 mm x 4 mm 40 mm x 5 mm |
|
round steel |
diameter: 10 mm |
diameter: 10 mm, 12 mm, 13 mm |
Earth rods |
mild steel tube angular steel or other similar sectional or round steel |
diameter: 24 mm min. wall thickness: 3 mm 40 mm x 40 mm x 4 mm |
diameter: 33.5 mm (1) diameter: 60 mm (2) 40 mm x 40 mm x 4 mm |
Earth leads are interconnected by screwed, clamped and welded connections.
- Contact lines.
Contact lines are used for electromobiles with and without longitudinal carriers including safety stop cables. Conductors of sectional rails in workshops, on ceilings, under bridges, in tunnels and passages are also belonging to the contact lines.
Table 8 Contact lines, types and use
Designation |
Material |
Type of section |
Purpose of use |
Steel-copper contact line |
Contact line with steel core and copper sheathing |
|
No high resistance to wear, suitable for subsidiary routes with normal traffic and low speeds 1 copper sheathing 2 steel core 3 groove for fixing purposes |
Copper contact wire |
Solid copper section |
as above but without steel core |
Ri 80, Ri 100, Ri 120. use for standard-gauge railways |
Steel contact line |
All-steel contact line |
|
For replacement purposes only, for short routes with little traffic |
0 Steel current bar (rail) |
Sectional steel rail with aluminium reinforcement |
|
High resistance to wear, suitable for city or underground railway routes as feeder bar beside the track (only when provided with its own track bed - self-contained facilities) 1 steel rail section 2 aluminium subsequently or additionally added to enlarge the cross section 3 pick-up sides |
Flat-section type |
Copper or bronze |
|
For small contact wires, crane tracks, conveyor equipment |
Round-section type |
Copper or copperbase alloys, bronze etc. |
|
For crane equipment, conveyor equipment |
- Overhead lines
These are open-type lines installed overhead in the open air with span lengths of normally more than 20m.
In order to place overhead lines out of reach of man and to ensure freedom of motion for vehicles of any kind, poles are required for overhead lines. Overhead lines of up to 1000 V, for example, are fixed on pin-type insulators or shackle insulators. Cap-and-pin insulators or long-rod insulators are used for rated voltages of more than 1000 V.
Figure 24. Types of poles - (1)
supporting pole (straight-line pole), e.g. wooden pole with reinforced concrete
pole footing, (2) angle pole, e.g. wooden pole with anchor, (3) angle pole, e.g.
wooden pole with tie, (4) terminal pole, e.g. wooden A-pole (anchor and terminal
pole) 1 wooden pole, 2 reinforced concrete footing, 3 anchor, 4 tie
Figure 25. Pole head types - 1 use
in the voltage range 0.4 to 6 kV as wooden pole or reinforced concrete pole, 2
use in the voltage range 6 to 20 kV as concrete pole (the central conductor is
alternatingly run at the right-hand and left-hand side of the pole), 3 use for
voltages of more than 20 kV up to about 220 kV as lattice steel pole
Figure 26. Insulators - 1, 2
pin-type (rigid-type) insulators, 3 shackle insulator, 4 cap-and-pin insulator,
5 long-rod insulator
- Open-type lines
Open-type lines include, for example, short connection lines in the area of buildings (over courtyards, between workshop halls etc.).
- Stranded conductors
Stranded conductors are multi-wire conductors which are movable because of their flexible construction.
- Earthing wires
Earthing wires are used to protect voltage-carrying conductors against direct lightning stroke or to carry off to the soil over-voltage of atmospheric or other origin and consequently to avoid or reduce step and contact voltages on poles and scaffoldings.
Marking of bare lines
Table 9 Identification colour codes for power transmission lines
Type of current |
Conductor |
Colour code |
D.C. |
L+ |
red |
|
L- |
blue |
|
M |
light-blue |
Three-phase current |
L 1 |
yellow |
|
L 2 |
green |
|
L 3 |
violet |
|
N |
light-blue |
A.C. |
L 1 |
yellow |
|
L 2 |
violet |
Table 10 Identification colour codes for protective earthing and system earthing lines
Type of earthing |
Colour code |
Protective earth |
black |
System earth |
white with black cross-stripes |
Joined protective earth and system earth |
from the point of joining: black with white cross-stripes |
Table 11 Identification colour codes for earthing lines from the conductor to the earth
Type of current |
Conductor |
Main colour |
Identification colour additional colour as cross-stripes |
Direct current |
L+ |
black |
red |
|
L- | |
blue |
|
M | |
white |
Three-phase current |
L 1 | |
yellow |
|
L 2 | |
green |
|
L 3 | |
violet |
|
N, PE | |
white |
|
PEN |
| |
Single-phase A.C. to IEC |
L 1 |
black |
yellow |
|
L 2 | |
green |
for raiIway facilities |
L 1 |
|
yellow |
|
L 3 | |
violet |
Two-phase A.C. |
L 1 |
|
yellow |
|
L 2 | |
green |
Insulated lines
- Construction
Insulated lines consist of a single insulated conductor or of multiple conductors insulated from each other and are provided with protection against impairment of the electric function. Normally they are not allowed for laying in soil and water.
· Conductor
Material:
aluminium or copper, Type of conductor: single-wire, multi-wire or poly-wire,
fine-wire or extra-fine wire.
Shape of cross section: round.
· Insulating
cover
consisting of rubber, plastic material, glass silk or artificial silk.
· Sheathing
consisting of
rubber or plastic material.
- Wire marking
The insulating covers of multi-wire lines are marked with a colour code for safety reasons and for quicker working.
· Protective conductor
Colour code of protective conductor: green-yellow,
The green-yellow wire may only be used as protective conductor or auxiliary earthing wire.
· · Multi-wire lines are produced with or without protective conductor
· · With flat lines, the wire with the relevant colour code is to be used as protective conductor.
· · Wire marking
Table 12 Wire marking
Number of wires |
Lines with protective conductor |
Lines without protective conductor |
1 |
gnge |
b1 |
|
b1 |
sw or br |
|
sw or br |
|
2 |
gnge sw (only for fixed laying) |
b1 sw or br |
3 |
gnge b1 sw or br |
b1 sw br |
4 |
gnge b1 sw br |
b1 sw br sw |
5 |
gnge b1 sw br sw |
|
Gnge |
green-yellow |
br |
brown |
b1 |
blue |
sw |
black |
- Abbreviations
All countries are aiming at standardized abbreviations for marking and identification. The following markings are an example:
· Group markings
A wire line
D triple line
F |
flat line (ribbon conductor) |
Fr |
overhead line (wire or rope) |
H |
hose line |
I |
installation line (wiring line) |
Kr |
motorcar supply line |
L |
tubular lamp line |
N |
heavy-current line |
P |
testing and measuring line rubber-sheathed line for mines |
Rö |
X-ray line |
S |
special line |
Sch |
welding line |
T |
trailing line |
TS |
trailing line, multi-wire |
TM |
trailing line, single-wire |
W |
heater line |
Z |
twin line |
Zü |
ignition line |
· Constructional elements
C |
shield of metallic wires or conductive layer |
CE |
like C, but around each wire |
G |
insulating cover or sheathing of elastic material (rubber) |
2G |
insulating cover or sheathing of silicone rubber |
GS |
insulating cover, protective cover or fibre core of glass silk |
St |
control wire (St) shield of metal foil |
T |
carrying member |
TX |
textile fibre core |
U |
outer braiding |
Ü |
supervisory wire |
Y |
insulating cover or sheathing of PVC |
2Y |
insulating cover of polyethylene |
· Additionally marked porperties of the line
fl |
flat |
h |
increased electric strength |
k |
increased resistance to cold |
1 |
specially light-resisting |
ö |
oil-resisting |
öu |
oil-resisting and non-inflammable |
s |
increased wall thickness |
t |
increased heat resistance |
u |
non-inflammable |
· Additionally marked properties af the conductor
b |
poly-wire |
e |
single-wire |
f |
fine-wire |
m |
multi-wire |
m/v |
multi-wire/compressed |
vz |
tin-plated |
w |
helical |
z |
increased tensile strength |
· Colour code abbreviations
b1 |
blue |
br |
brown |
dgn |
dark-green |
el |
ivory |
ge |
yellow |
gn |
green |
gnge |
green-yellow |
gr |
grey |
nf |
natural-coloured |
sw |
black |
ws |
white |
Figure 27. Insulated line - 1
sheathing, 2 insulating cover, 3 conductor
Table 13 Composition of abbreviations
- Insulated power lines for fixed laying - examples
· Lighting line
Abbreviation: NLZYF 2 x 0.5 - ws - (Un = 300/300 V). Fine-wire Cu-conductor, plastic (PVC) insulating covers. Both wires are in parallel. Preferential colour: white. Application: in and at lamps with fixed laying. For dry and sometimes damp rooms, in and at lamps.
· Plastic-insulated line
Abbreviation: NAYY-J 2 x 2.5 re - 1 kV - (Un =1 kV). Single-wire, round Al-conductor, plastic (PVC) insulating covers and sheathing with green-yellow wire. Universally applicable in all media for wiring and control purposes.
· Plastic-insulated wire line
Abbreviation: NY b 10 - bl - (Un = 300/300 V). Poly-wire Cu-conductor, plastic (PVC) insulating cover, wire line for protected laying (wiring). For installations, in and at machines, in cases of vibrations and frequent bending stress, in dry and sometimes damp rooms.
Table 14 Places of installation and examples of applications of insulated power lines for fixed laying
Type of line |
Abbreviation |
Rated 3) voltage |
Application 2) Place of installation |
Examples of applications | |||||||
- |
- |
kV |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
-- |
Lighting line |
NLZYF |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
- |
in and at lamps |
Tubular lamp line |
NL2YY |
7.5/7.6 |
x |
- |
- |
- |
- |
- |
- |
- |
advertisement illumination, |
|
NL2YCY |
7.5/7.5 |
x |
x |
- |
- |
x |
x |
x |
x |
particularly outdoors |
Rubber-sheathed line |
|
|
| | | | | | | |
|
|
NIAGGöu |
0.45/0.45 |
x |
x |
- |
- |
- |
- |
- |
x |
for illumination purposes |
Silicone rubber- sheathed line |
N2G |
1 1) |
x |
- |
- |
- |
- |
- |
- |
x |
in lamps, in and at thermic |
|
N2Gf |
| | | | | | | | |
appliances, in hot rooms |
Installation lines |
NIAZY |
0.3/0.3 |
x |
- |
- |
- |
x |
- |
- |
- |
flush with intermediate ceiling installation |
|
NIDAY |
0.3/0.3 |
x |
- |
- |
- |
x |
- |
- |
- |
buried in bulk walls and ceilings and with underfloor and intermediate ceiling installation |
Plastic-insulated cable |
NYYD NYY |
1 |
x |
x |
x |
x |
x |
x |
x |
x |
universally applicable for wiring and control purposes |
|
NAYYd |
| | | | | | | | |
|
|
NAYY |
| | | | | | | | |
|
Plastic-sheathed line |
NIYYf1 |
0.3/0.5 |
x |
x |
- |
- |
x |
x |
x |
x |
for wiring and control purposes |
|
NIAYYf1 |
| | | | | | | | |
|
|
NILAYYf1 |
| | | | | | | | |
|
Plastic-insulated wire line |
NY |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
- |
for installations, in and at machines, in cases of vibrations or frequent bending stress |
|
NYb |
| | | | | | | | | |
|
NAY |
| | | | | | | | | |
|
N2AY |
| | | | | | | | |
|
Special-purpose |
NSYb |
0.6/1 |
x |
- |
- |
- |
- |
- |
- |
- |
for ships, rail vehicles |
plastic-insulated |
NSYf |
| | | | | | | | |
|
wire line |
|
| | | | | | | | |
|
Rubber-insulated |
NGUb |
0.6/1 |
x |
- |
- |
- |
- |
- |
- |
- |
rail vehicles |
wire line |
|
1.8/3 | | | | | | | | |
|
|
|
3.6/6 | | | | | | | | |
|
|
NGUf |
0.6/1 | | | | | | | | |
|
|
|
1.2/2 | | | | | | | | |
|
special-purpose |
NSGGföu |
1.8/3 |
x |
x |
- |
- |
- |
x |
x |
- |
rail vehicles |
rubber-insulated |
NSGCGföu |
and | | | | | | | | |
|
wire line |
NSGCGföuk |
3.6/6 | | | | | | | | |
|
Explanations of the figures
1)
up to 1.5 square millimetres rated voltage 300/500 V
from 2.5 square millimetres rated voltage 450/750 V
2)
1 dry and sometimes damp rooms
2 damp or wet rooms or
outdoors
3 in soil
4 in water
5 flush or buried
6 on the surface, on
trays and supporting brackets
7 on wood, cardboard, particle board or
fibreboan
8 when there is a possibility of direct contact of the line
3) Rated voltage indicated as conductor-earth voltage/conductor-conductor voltage
- Insulated power lines for portable equipment - examples
· Triple line
Abbreviation: NDY 3 x 0.75 - gr - (Un = 300/300 V). Fine-wire Cu-conductor, plastic (PVC) insulating cover. The three wires are in parallel. Colour: grey. For light portable devices (kitchen appliances, radio and TV sets), no thermic appliances and no extension line, in dry and sometimes damp rooms and when there is a possibility of direct contact of the line.
· Light plastic hose line
Abbreviation: NHYY1 3 x 0.75 - gr - (Un = 300/300 V). Fine-wire Cu-conductor, plastic (PVC) insulating covers and sheathing. Colour of sheathing: grey. For office machines, vacuum cleaners, refrigerators, in dry and sometimes damp rooms and when there is a possibility of direct contact of the line.
· Medium shielded plastic hose line Abbreviation: NHYYCY 3 x 1 - gr - (Un = 300/500 V). Fine-wire Cu-conductor, plastic (PVC) insulating covers, inner and outer sheathing. Shield of Cu-wire mesh. Colour of sheathing: grey. For medium mechanical stress, extension lines, shielding electric fields, for control purposes, in dry and wet rooms, in the open air, in water, on wood, cardboard, particle board and fibreboard and when there is a possibility of direct contact of the line.
Table 15 Places of installation and examples of applications of insulated power lines for portable equipment
Type of line |
Abbreviation |
Rated voltage |
Application Place of installation |
Examples of applications | |||||||
- |
- |
kV |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
- |
Twin line | |
| | | | | | | | |
light portable devices, |
Triple line |
NZY |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
x |
no thermic appliances and extension lines |
Plastic hose lines: especially light light |
NDY |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
x |
|
|
NHYY11 |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
x |
|
|
NHYY1 |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
x |
office machines, vacuum |
|
NHYY1f1 |
| | | | | | | | |
cleaners, refrigerators |
medium |
NHYY |
0.3/0.5 |
x |
x |
- |
x |
- |
- |
x |
x |
for medium mechanical stress, extension lines |
medium shielded |
NHYYCY |
0.3/0.5 |
x |
x |
- |
x |
- |
- |
x |
x |
like NHYY, shielding of electrical fields, for control purposes |
with supporting facilities |
NHT2YY |
0.3/0.5 |
x |
x |
- |
- |
- |
x |
x |
x |
for high tensile stresses, such as |
with supporting facilities and shielded |
NHT2YCY |
0.3/0.5 |
x |
x |
- |
- |
- |
x |
x |
x |
elevators/lifts |
Rubber hose lines: with textile braiding |
NHGGU1 |
0.3/0.3 |
x |
- |
- |
- |
- |
- |
- |
x |
light thermic appliances, electrothermic appliances, extension lines |
light |
NHGG1 |
0.3/0.5 |
x |
- |
- |
- |
- |
- |
- |
x |
for medium mechanical stresses, workshop devices, tools, also outdoors, agricultural imple ments |
Rubber hose lines: heavy |
|
| | | | |
1) | | | |
|
|
NSH |
0.6/1 |
x |
x |
- |
x |
- |
x |
x |
x |
for higher mechanical stresses, |
|
NSHöu |
| | | | | | | | |
construction machinery, heavy |
|
NSHöuk |
| | | | | | | | |
workshop equipment |
|
NSHCk |
| | | | |
1) | | | |
|
heavy with sup porting facili ties |
NSHT |
0.45/0.75 |
x |
x |
- |
x |
- |
x |
x |
x |
for high tensile stress (control purposes in shafts and on hoist ing gears) |
|
NSHTöu |
| | | | | | | | | |
Rubber hose lines for mines |
|
| | | | |
1) | | | |
for underground mines, in pits |
|
NOö |
0.6/1 |
x |
x |
- |
x |
- |
x |
x |
x |
with firedamp and explosion hazards |
with supervisory conductor |
NQÜö |
0.45/0.75 |
x |
x |
- |
x |
- |
x |
x |
x |
like NQö but with supervisory |
Welding line |
NSCHGöu |
0.12/0.2 |
x |
x |
- |
- |
- |
x |
- |
x |
interconnection line between transformer and electrode holder |
Trailing line |
|
| | | | |
1) | | | |
|
single-wire |
NTM |
1.8/3 |
x |
x |
- |
x |
- |
x |
x |
x |
for high mechanical stress, con |
|
NTMöu |
3.6/6 | | | | | | | | |
nection of high-voltage motors |
|
NTMCöu |
12/20 | | | | | | | | |
and power supply installations |
|
NTMCöuk |
18/30 | | | | |
1) | | | |
(peak-load stations) |
four-wire |
NTSCEöu |
3.6/6 |
x |
x |
- |
x |
- |
x |
x |
x |
as above, power supply for big |
|
|
6/10 | | | | | | | | |
equipment (excavators and |
|
NTSCEöuk |
12/20 | | | | | | | | |
conveyor bridges in open-cast |
|
|
18/30 | | | | | | | | |
lignite mines) |
1) except in mining, on building sites and for portable equipment
- Fabricated power lines - examples
These are industrial, standard lines with integral connectors.
· Mains connection lines
· · Abbreviation: A1-2-32/7 - gr -
Mains connection line (A1) with integral coupler plug, two-pin, 2.5 A (also called
European plug) for appliances of protection class II. Line: NZY 2 x 0.75 mm, length 2 m, dismantling length 32 mm, insulation-stripping length 7 mm. Colour: grey.
Application: mains connection of electrical appliances of up to I = 2.5 A. Not allowed in the open air and in wet rooms.
Figure 28. Mains connection line with
integral coupler plus 2.5 A
· · Abbreviation: EHI-4-63/7 - sw -
Mains connection line (EHI) with integral safety plug, 10/16 A, of plastic material and with increased degree of protection for appliances of protection class I. Line: NMH 3x1 mm2, length 4 m. dismantling length 64 mm, insulation-stripping length 7 mm.
Colour: black. Application: mains connection of electrical appliances of up to In = 16 A.
Allowed in the open air and in wet rooms.
Figure 29. Mains connection line
with integral safety plug 10/16 A
· Interconnection lines
Abbreviation: 22-1, 6-3-32/7 - sw -Interconnection line (Z2) with integral appliance lead-in of type 3 at one end. Line length: 1.6 m. Dismantling length 32 mm. Insulation-stripping length 7 mm. Colour: black. Application: interconnection line with fixed connection at both ends.
Figure 30. Interconnection line with
fixed connection at both ends - 1 with integral appliance lead-in, 2 with outer
braiding
- Not allowed laying of insulated lines
Table 16 Not allowed laying of
lines carrying voltage in
operation
Figure 31. Power cable - 1 conductor,
2 conductor insulation, 3 belt, 4 sheathing, 5 inner protective covering, 6
armouring, 7 outer protective covering
Construction
Cables consist of one or more insulated electric conductors. They are provided with one or more protective layers with properties allowing the cables to be laid in cable trenches, cement ducts or cable ducts and water without impairing the electric function.
(The cable construction is always considered from inside to outside)
Constructional elements
- Conductor
Material: aluminium or copper.
Type of
conductor: single-wire or multi-wire.
Shape of cross section: round, oval,
sector-type.
- Conductor insulation
Insulating cover may be made of
· polyvinyl chloride (PVC), for rated voltage 1 kV,
· polyethylene (PE), for rated voltage up to 30 kV,
· paper, well impregnated with cable impregnating compound up to 30 kV, impregnated with cable oil up to 380 kV (internationally)
- Core
Conductor with insulating cover.
- Belt
Paper insulation, well impregnated with cable impregnating compound, in several layers enclosing the core as additional insulation.
- Sheathing
Seamless lead, aluminium or plastic covering, protects the interior of the cable from external mechanical and chemical effects.
- Inner protective covering
Bitumen-impregnated paper layers with fluid intermediate bituminous compound which, in the event of mechanical stress (such as bending of the cable), permit pressure compensation between the metal sheathing or plastic sheathing and the cable armour.
- Armour
Material: steel.
Type: 2 layers of strip steel with protective coating against corrosion or round-wire armour, non-magnetized.
Type of wrapping: closed or open (round-wire armouring).
25 % overlapped (strip-steel armouring) and, against special order, anti-twist wrapping.
- Outer protective covering
Single protective covering of coarse tow yarn or textile tape with semifluid compound and non-sticking coating - A, double protective covering as above - AA, protective covering of PVC - Y. Cables with protective covering of impregnated fibre materials are allowed in rooms if impregnated against inflammability.
Classification
- Purpose
· control purposes,
· transmission of electric power.
- Voltage
· low voltage: ³ 42 V = 1 kV
(£ 42 V low voltage)· high voltage: medium voltage 1 to 30 kV.
extra-high voltage 110 kV.
- Construction
· compound-impregnated cable,
· plastic-insulated cable,
· oil-filled cable for extra-high voltages,
· special-purpose cable,
· plastic-insulated cable with more than five cores.
Wire marking
- Purpose
Marking of the wires largely precludes that the wires get mixed up and. therefore, is in the interest of higher reliability of service and easier installation.
Wire marking is not necessary for cable of more than 1 kV.
Up to 1 kV the wire marking corresponds, to a large extent, to that of lines. The marking of the protective conductor is of special importance.
The green-yellow wires are to be used as protective conductors.
- Type of wire marking
For the benefit of unmistakable definition of the type of wire marking (especially where two types are possible) of a multi-wire 1 kV cable, the letter code has been extended to include 3 and 0.
Examples:
NAYY-J 4 x 25 re 1 kV four-wire plastic-insulated NAYY cable with a wire marked green-yellow or with figure code 3-1-2-3.
NAYY-0 4 x 10 re 1 kV four-wire plastic-insulated NAYY cable with a nominal conductor cross section of up to 50 mm and the colour code gnge/b1/sw/br or with figure code 1-2-3-4.
NAYY 1 x 185 sm 1 kV
single-wire plastic-insulated NAYY
cable.
Table: Wire marking of 1 kV cables
Table 17 Wire marking of 1 kV cables
| |
Wire marking | |||
Type of cable |
|
by colours |
by figures, colours or letters | ||
| |
cables with green-yellow wire (letter J) |
cables without green-yellow wire (letter O) |
cables with a green-yellow wire or with a wire marked with the letter J (letter J) |
cables without a green-yellow wire or without a wire marked with the letter 3 (letter O) |
(1) |
|
(2) |
(3) |
(4) |
(5) |
Compound-impregnated cables |
single-wire |
nf or sw |
|
- |
- |
or plastic-insulated cable |
two-wire |
gnge/nf or |
- |
J-1 |
- |
more than 35 mm2 |
three-wire (also cables with concentric conductor or Al sheathing |
- |
nf/nf/nf or |
- |
1-2-3 |
|
four-wire |
gnge/nf/nf/nf or gnge/sw/sw/sw |
nf/nf/nf/nf or sw/sw/sw/sw |
3-1-2-3 |
1-2-3-4 |
NYY, NAYY, NYYd, |
two-wire three-wire four-wire five-wire |
gnge/sw |
b1/sw |
gnge-1 |
1-2 |
Plastic-insulated cables |
(2) direction wire in the outer stranding layer |
gnge |
br |
gnge |
- |
with more than 5 wires |
marked wire in each stranding layer |
b1 |
b1 |
1 to 36(1) |
1 to 37(1) |
|
other wires |
nf or sw |
nf or sw |
|
|
b1 blue, br brown, gnge green-yellow (for compound-impregnated cables green-natural-coloured), nf natural-coloured, sw black(l) Sequence of figures 1 to 37 from inside to outside
(2) Seven-wire plastic-insulated cables have one gnge-wire, plastic-insulated cables with more than 7 wires do not have a gnge-wire. Deviations are possible.
Note: When using the gnge wire marking, one of these colours should cover not less than 30 % and not more than 70 % of the wire surface of each 15 mm long wire portion,
Cable designation
To get clear and full information of the specific technical construction of a cable and to avoid extensive description, standardized abbreviations for cables are also aimed at. The following markings shall also serve as an example:
- Insulating cover
Y PVC insulating cover
2Y PE insulating cover
O oil
insulation
- Shield
H shield of wire
- Concentric conductor
For 1 kV cables with an electrically effective cross section of
Fa |
flat-wire aluminium |
Fu |
flat-wire copper |
Ra |
round-wire aluminium |
Ru |
round-wire copper |
For |
1 kV cables with an electrically effective cross section of |
Ca |
aluminium |
Cu |
copper |
- Sheathing
K |
lead sheathing |
Ka |
aluminium sheathing |
Y |
PVC sheathing |
- Armour
B |
strip-steel armouring |
Ba |
aluminium armouring |
BY |
rigid-PVC armouring |
R |
round-wire steel armouring |
G |
anti-twist steel armouring |
- Protective covering
A |
single protective covering |
AA |
double protective covering |
Y |
PVC protective covering |
- Protection against corrosion
· K |
single protection |
· KK |
double protection |
(Letter is omitted for cables with sheathing or concentric conductors of aluminium.)
- Types of conductors
e |
single-wire |
m |
multi-wire |
r |
round |
s |
sector-type |
- Additional marking of constructional elements
o |
open-type armouring, e.g. Ro |
w |
corrugated constructional element Kaw |
z |
hardening additive Kz |
v |
cross-linke |
d |
2Yv d twist-marked Yyd |
- 1 kV cables
J |
with green-yellow wire or with wire figure |
0 |
without green-yellow wire or without wire figure 0 |
- Examples
NYKY |
plastic-insulated cable with Cu-conductors, lead sheathing and plastic protective covering |
NAYKY |
plastic-insulated cable with Al-conductors, lead sheathing and plastic protective covering |
NAYY |
plastic-insulated cable with Al-conductors and plastic sheathing |
NAKY |
paper-insulated compound-impregnated cable with Al-conductors, lead sheathing and plastic protective covering |
···· A |
outer protective covering of coarse tow yarn or textile tape with semifluid compound and non-sticking coating |
··· Y |
with outer protective covering of PVC |
··· BA |
with strip-steel armouring and outer protective covering of coarse tow yarn or textile tape |
··· RoA |
with open-type round-wire steel armouring and outer protective covering of coarse tow yarn or textile tape |
··· RG |
with anti-twist round-wire steel armouring |
NY2YHCaY |
polyethylene-insulated cable with wire shields, concentric conductor of aluminium strips and flat-wire aluminium, PVC sheathing |
Note:
In the case of copper conductors the A is omitted after the N in the abbreviation.
Manufacturing types
- Compound-impregnated cables
Paper-insulated power cables. Single-wire or multi-wire low-voltage or high-voltage cables with compound-impregnated or compound-impregnated and drained paper insulation. They may have a metal sheathing cladding all or individual wires and, in addition, special protective coverings, depending on the purpose of use.
- Belted cables
The simplest cable from the manufacturing point of view. They are produced with three or four wires.
· Properties
The poor thermal conductivity of the belt increases the heating of the cable. The impregnation compound presses outwards, cavities are formed inside. Increasing danger of glow discharge, enhanced by increased rated voltage.
· Use
In installations with rated voltages of up to 10 kV.
- Hoechstaedter cables (H-type cables)
Cables with individual shielding of the wires, without belt.
· Properties
The mutual contact of the wire shielding and metal sheathing (electrically conductive) restricts the electric fields to the wire insulation
· Use
In installations with rated voltages of up to 30 kV.
- Single-conductor cable
Differs from the normal construction of cables. Expensive manufacture.
· Properties
Good thermal conductivity, thus higher current-carrying capacity; high short-circuit strength (When laid on cable trays, registers etc. and on cable lifting points at terminal boxes, special measures of fixing of the cables may be required in view of the high dynamic effects of possible short-circuit currents); easy instal-lation and repair. Higher additional losses because of magnetic fields inside the cables and of mutual magnetic influence of several cables (three-phase systems)
· Use
In D.C. and three-phase installations of any rated voltage.
- Separate lead type cables (SL-type cables)
Combination of three single-conductor cables - without pressure protection and armouring - into one cable.
· Properties
The greater mass of metal (metal sheathings) results in better thermal conductivity, thus good electric shielding of the conductors against each other, reduction of losses.
· Use
In 20 kV and 30 kV installations.
- Plastic-insulated cables
Plastic-insulated cables are cables with plastic material used as insulating, filling and sheathing materials.
· Advantages compared to compound-impregnated cables The costs of manufacturing and processing of plastic-insulated cables are considerably lower than those of conventional cable manufacture and processing. Advantages include: considerably smaller mass, better colour coding, higher elasticity and easier processing.
· Use
In installations with rated voltages of up to 30 kV.
· Types
Cables with plastic-insulated cores and plastic inner sheathing, armouring and outer covering, such as NAYBY.
Cables with plastic-insulated cores, concentric outer conductor and plastic outer sheathing, such as NAYFaY.
The various plastic coverings are chemically composed according to the relevant purpose, i.e. sole purpose of insulation (dielectric strength, core insulation), sole purpose of filling (filling of cavities, filler material) as well as purposes of protection against chemical and mechanical influences (outer sheathing)
· Polyethylene (PE) proved to be particularly suitable as raw material for core insulations and sheathings.
- Special-purpose cables
This term covers all cables for special purposes of use:
· Power cables for ships NMYCY.
· Aerial cables NLAYYT, NLA2YvHCaeYT.
· Radiation-proof cables NXGG.-
Such cables are exposed to extraordinary conditions at the place of installation, such as high thermal and chemical as well as extreme mechanical stresses.
- Plastic-insulated cables for control and information purposes They differ from power cables by a higher number of cores (7 to 37 cores) and a cross section ranging from 1.0 to 6.0 mm Cu and 2 2.5 to 6.0 mm Al. They are produced as plastic-insulated cables.
· Properties
Special colour code and a specific way of counting the cores.
Compared to multi-conductor cables of the same cross section, the load on the cores is considerably lower because of the very poor heat dissipation (massing of cores).
· Use
Such cables are generally produced up to a rated voltage of 1 kV only and used in heavy-current installations for measuring, signalling and control purposes.
Standard system of modular vessels
It is a modern system of modules that can be universally combined and be used in electrical and electronic engineering. Such a system enables a high packaging density in electrical installations/plants.
The vessels serve for covering and/or housing of components, modules, subassemblies, units and devices. The vessels can be classified in groups of order.
- Zeroth order vessels
Circuit cards, card plug-in units (non-protected), card inserts (non-protected)
Use:
The assembled printed circuit boards of standard sizes including plug-and-socket-connectors or terminal connectors are intended for use in vessels of 1st or 2nd order.
- First order vessels
Plug-in units and card inserts (protected), card plug-in units and card inserts (shielded), rack plug-in modules, rack inserts. Use:
As complete modules, mostly as self-contained functional units.
- Second order vessels
Sub-racks, plug-in subassemblies, subassembly inserts, card inserts.
Use:
As rigidly built-in or plug-in units they are used, for example, to complete the tiers in a cabinet. Together with the zeroth order vessels they fulfil the mechanical functions.
- Third order vessels
Built-in vessels, mounting vessels, box-type vessels, panel vessels, racks, cabinets, outdoor cabinets, control-room cubicles, consoles, desks.
Use:
They are the outer enclosure of the final product and have a decisive influence on the degree of protection, climatic class etc. Besides the front panels, they determine the shape of the final product. In connection with the 2nd order vessels they ensure the mechanical functions.
- Fourth order vessels
Subcarriers, plug-in unit carriers, insert carriers, mounting racks, swing-out racks.
Figure 32. System structure of indoor
switching plants using the standard system of modular vessels (1.1 switchboard
section. 2.2 contactor section, 1.3 capacitor section, e.g. of 400 mm mounting
depth), (2.1 switchboard section, 2.2 contactor section, 2.3 capacitor section,
e.g. of 800 mm mounting depth), 3 subsidiary distribution, 4 energy
distribution, 5 transformer box, 6 peak-load centre, 7 busbar module, 8
structural head of an indoor switching plant
Indoor switching plants
- Use
Switchboard sections, contactor sections and capacitor sections are intended for universal use as main and subsidiary distributions. All sections of the same mounting depth can be combined with each other. The sections of 800 mm mounting depth can be combined with transformer boxes into peak-load centres (see also Fig. 32).
- Construction
Each section has a busbar chamber, an equipment chamber and a cable termination and current bar chamber to connect the equipment modules.
- Equipment modules
Plug-in sub-units, plug-in units or inserts to be mounted in the sections. Plug-in units are connected through plug contacts, inserts are rigidly built in and connected.
- Sections
The different sections are:
· Switchboard sections with on-load switches, power circuit breakers, fuses, contactors, no-load switches, relay modules for information processing.· Contactor sections with contactor outlets for various circuits and rated currents.
· Capacitor sections with capacitors for power-factor compensation.
· Electric power distributors with power switches, NH-fuse outlets, break-jack points, busbars and/or combinations for use in power supply substations.
· Subsidiary distributions with current-limiting power switches, on-load switches and fuses.
· Transformer boxes with dry-type transformers up to 1000 kVA.
Figure 33. Front view of an indoor
switching plant as peak-load centre (example)
Sheet steel-enclosed low-voltage distributing plants (SLD system)
The SLD system offers a variety of possible combinations with a minimum number of component parts.
- Construction
Sheet steel enclosure of standard size to house switchgear, transducers, meters, measuring instruments, transformers, pushbutton switches, signal devices and busbars. The assembled complete distributions are mounted on supporting racks.
- Use
Wherever electrical devices are to be protected against moisture, dust and mechanical damage. They are particularly suitable for industrial, mining and metallurgical operations and building sites.
Figure 34. SLD mounted on supporting
rack with connection lines
Figure 35. Example of a specifically
assembled SLD - 1 general connection diagram, 2 assembly of casings
Standard Box System (SBS)
A metal (aluminium alloy) or plastic box with the relevant components already mounted by the manufacturer.
- Construction
Table 18 Metal type SBS for IP54 and partly for IP56
Empty boxes |
Appliance boxes |
Accessories |
Screw caps (5 sizes) |
Juntion boxes |
Cable terminal boxes |
|
Fuse boxes |
Flanged caps |
|
Barrier boxes |
Insert bowls |
Screw caps (4 sizes) |
Switches |
Sealing sheets |
|
Terminal boxes |
Potential equalization rails |
|
Repair switch boxes |
Quick-seal couplings |
|
Ballasts |
Protective conductor rails |
| |
Special accessories |
Table 19 Plastic type SBS for IP 54
Empty boxes |
Appliance boxes |
Accessories |
Screw caps (3 sizes) |
Junction boxes |
Cable terminal boxes |
|
Fuse boxes |
Insert bowls |
|
Barrier boxes |
Sealing sheets |
|
Terminal boxes |
Protective conductor rails |
|
Base-mounted sockets |
|
|
FDSP, 16 A | |
- Use
· Plastic boxes are only used in installations/plants with temperatures up to 60°C. They are very corrosion-resistant.· Metal boxes are universally applicable under extreme conditions. The IP 56 version is mainly intended for use in shipbuilding.
Low-voltage cabinet distributing system (LCD system)
- Construction
Sheet steel enclosure with mounting frame
The mounting frame serves for fixing of the devices and for holding of the device covers. After mounting and wiring it is bolted in the cabinet.
Cabinet distributors can be provided with D-fuse sockets up to B33, NH-fuse sockets up to size 1, gang switches up to 25 A, cam switches up to 100 A, air-break contactors up to IDS, motor protection switches, adapting transformers, automatic cut-outs and meter boards.
- Use
LCD systems are used in housing and social building construction, in industry and agriculture.
Figure 36. Example of a central house
connection box
Figure 37. Example of a distributing
cabinet for a house wiring system
Outdoor switching and distributing cabinets
Cabinets for switching purposes and distribution of electric energy, e.g. for use in the building industry, in traffic engineering, rail-way facilities, street lighting, agriculture, on building sites.
Figure 38. Example of a cable
terminal box 1 equipment support
Medium-voltage switching stations, substations and transformer stations
- Switchgear cubicles (cells)
Of metal-enclosed or open (solid insulation) type, they are used as line and on-load switch cubicles, cable and measuring cubicles in switching stations for industrial power supply (metal-enclosed types) or in closed electrotechnical rooms, particularly for switching of transformers, and on heavy open-cast mining equipment (solid insulation).
Table 20 Technical data of switchgear cubicles
Switchgear cubicle |
Insulation voltage |
Rated current | ||
Metal-enclosed type |
12 kV | |
1250 A | |
| |
|
or 2500 A | |
Solid insulation type |
36 kV | |
1250 A |
- Substations
Buildings mostly constructed from industrially prefabricated assemblies, brickwork or concrete. They serve to transmit the electric energy through cables to the medium-voltage and low-voltage levels. They have separate medium-voltage and low-voltage chambers.
Figure 39. Example of the layout of a
substation with cable connections - 1 cable entries/exits, 2 transformer
chamber, 3 low-voltage switching plant chamber, 4 medium-voltage switching plant
chamber
· Equipment
· · Medium-voltage switching plant 6 and 10 kV with semi-open or sheet steel-enclosed switchgear cubicles 15 and 20 kW with sheet steel-enclosed switchgear cubicles 30 kV with solid-insulation switchboard sections· · Low-voltage switching plant with indoor switching equipment having the following purposes or functions: connection of oil-filled transformers up to 1600 kVa, station service distribution, emergency power plant (accumulators), measuring processes, connection to earth, lighting installations.
- Transformer stations
Cable stations, overhead-line stations, pole stations and outdoor stations.
· Cable stations
Buildings of brickwork, concrete or industrially prefabricated assemblies. They are used as local network stations and for small or medium industrial plants.
Figure 40. Example of a local
network transformer station (layout) 1 transformer, 2 indoor switching plant, 3
switchgear cells. 4 relays, 5 accessories
· Overhead-line stations Buildings like cable stations. They are used as terminal station or through-station for local networks and smaller industrial plants.
Figure 41. Example of an
overhead-line through-station - (1) schematic circuit, (2) external view
· Pole stations
Transformers up to 160 kVA are erected on a platform at the overhead-line pole. They are used for overhead line systems in thinly populated areas with low power consumption.
· Outdoor stations
Transformer stations for temporary supply of electric energy for building sites, mining projects, mass events etc.
They are enclosed and can be moved on skids or wheels.
Figure 42. Schematic drawing of an
enclosed outdoor station on skids - 1 medium-voltage switching plant, 2
transformer, 3 low-voltage switching
plant
General
Switches are devices to open (break) and close (snake) current paths with all parts necessary for connecting or disconnecting firmly mounted on a joint base.
The force necessary for changing the switch position (ON/OFF) is provided by switch drives, such as
- hand drive
- magnet drive
- motor drive
- compressed-air drive
Low-voltage switches
The following types are in use:
- No-load switches
They must only be switched without load.
- On-load switches
They are designed for switching under load. Different types are:
· Installation (or house-wiring) switches
On-load switches designed for low-voltage electrical installations in rooms of residental buildings, industrial buildings and annexed buildings.
They are designed for a rated voltage of 250 V and for rated currents of 6 A and 10 A. They are classified according to
· · the mode of switching (e.g. cut-out switch, two-way switch, intermediate switch), the mode of driving (e.g. toggle switch, rocker switch, rotary switch, push-button switch),· · the type of installation (surface switch, flush switch, appliance switch),
· · the place of installation (e.g. moisture-proof switch, explosion-proof switch).
· Remote-controlled installation switches
Electromagnetic switches controlled by a low voltage of 12 V or by 220 V
· They are used in residental and social buildings.
- Overload circuit breakers
They are mainly used as motor switches to master high starting currents. They are tested by 10 to 20 times the rated current. Different types are:
· packet cam-operated switches,
· contactors,
· thermal relays,
· vacuum contactors,
· current-limiting power switches.
High-voltage switches
The following types are in use:
- Disconnectors.
- Load-break switches.
- Power switches.
For bare lines
- Holders:
insulated supports,
line-supporting fans or plates,
low-voltage and high-voltage overhead-line insulators,
bushing insulators.
- Line poles:
straight-line poles,
angle poles with anchors or ties,
terminal poles,
wooden poles,
reinforced concrete poles,
lattice steel poles.
- Conductor joints:
crimp joints,
screw and rivet joints,
cone joints,
seam joints,
jointing links,
jointing sleeves,
weld joints.
For insulated lines
- Holders:
clips (single and multiple types, nail, screw, louvre, spacer, series clips, anchor logs, register clips, single-tab and double-tab, with wall bolt),
supporting straps,
conduits,
duct systems,
surface sypes,
buried types,
bracing wire.
- Branch boxes, conduit boxes, switch boxes.
- Switches, sockets.
- Lighting fittings.
- Meter boards.
- Distributions.
For power cables
- Terminal boxes (sealing ends)
· For plastic-insulated cables:
wrapping terminations (indoors),
cast-resin terminations (outdoors).
slip-on and casing terminations (indoors and outdoors).
· For compound-impregnated cables:
cast-resin terminations (indoors),
hose terminations (indoors),
casing terminations (indoors and outdoors).
- Multiple-joint boxes:
For distribution of the individual cable cores of multi-core cables with joint sheathing.
Installation only in connection with single-conductor terminal boxes.
Figure 43. Multiple-joint box 1
multiple-joint box, 2 metal conduit. 3 single-conductor terminal box
- Distribution clips:
For distribution of separate lead type cables with each cable core with sheathing ending in a single-conductor terminal box.
Figure 44. Distribution clip (end
clip) 1 end clip, 2 metal sheathing, 3 single-conductor terminal box
- Cable sleeves.
- Compensation tanks:
For compensation of the quantity of the impregnation compound in compound-impregnated cable installations or for compensation of the oil pressure in oil-filled cables or oil-filled cable installations.
Figure 45. Example of a compound
compensation tank arrangement 1 connecting piece, 2 formed bend, 3 joining
piece, 4 joining T-piece, 5 connecting branch, 6 compound compensation tank. 7
minimum level of compensation tank, 8 single-conductor terminal boxes, 9
single-conductor or separate lead type cables, 10 multiple-joint box. 11 three
conductor
cable
Purpose
Insulators shall insulate current-carrying electric conductors with respect to other conductive parts which are not intended for current conduction.
Materials
- Porcelain is the material mostly used. It is age-resistant, corrosion-resistant, has a high mechanical strength and is a good insulator. Porcelain is used for indoor and outdoor low-voltage and high-voltage installations.
- Thermoset plastic material is non-corrosive, has a high mechanical strength and is a good insulator but it is aging and temperature-sensitive.
- Hard paper (laminated paper) has a high mechanical strength, is a good insulator but sensitive to moisture and aging. Thermoset plastic material and hard paper are only used for indoor low-voltage installations.
Stress
- Electric stress
The insulators must be designed so as to preclude breakdown or spark-over from the electric conductor to parts of the installation which are not belonging to the electric circuit. Moisture and dirt deposit are favourable for voltage spark-over.
- Mechanical stress
The insulators in overhead-line installations are subjected to tensile stress to all sides. The tensile stress is constantly varying, depending on the weather conditions (e.g. wind, hoar-frost, temperature variations) and the effects of electromagnetic forces between the conductors. In indoor installations there is mechanical stress only by electromagnetic effects between the conductors, i.e. by cantilever force and short-circuit force.
- Thermal stress
Temperature variations in the environment and in the lines have effects on the fastening elements between the conductor and insulator. Different heat conductivity and expansion coefficients result in mechanical stress which, in extreme cases, can destroy the insulator.
Damage to the conductor or insulator of any line or cable may occur as a result of improper transportation, wrong storage and inexpert laying as well as of fixing contrary to regulations. Insulated lines and cables are especially susceptible to damage.
Information required for the selection of lines or cables
Table 21 Information required for the selection of lines or cables
Type of information required |
Explanation |
1. Amount of load current |
Operating current |
2. Amount of rated voltage |
Low, medium or high voltage |
3. Type of laying medium |
Air, water, soil |
4. Type of laying |
Single laying, parallel laying, bunch laying |
5. Place of laying |
Indoors, outdoors and in soil, in waters, in swampy ground, in corrosion-developing environment, on bridges and with altitude differences |
6. Ambient temperature |
Average operating values |
7. Mechanical stress, if any |
Impact, shock, compression, tensile or bending stress |
In any laying of lines or cables it is to be guaranteed that the lines and cables are fail-safe. This includes
- protection against mechanical damage, e.g. by covering caps, conduits,
- protection against earth displacement, constant vibrations,
- protection against chemical damage,
- protection against excessive heat.
Mechanical stress
The lines and cables must resist bending, tensile and compressive stress.
To resist frequent, varying bending stress, the conductor can be divided into several partial conductors of small cross section. Bandages and armouring are measures to resist compressive stress.
Thermal stress
- Temperature
The temperature of a conductor depends on the current density (measured in A/mm). the material and the possibility of heat dissipation.
- Lines in bunches
Because of poor heat dissipation, lines laid in bunches must not be operated with the maximum admissible rated load.
- Admissible heating
Excessive temperatures cause damage to the insulation (increased brittleness, shrinkage effects and charring, considerably reduced dielectric strength) which may result in breakdown with total failure of the line or cable.
Laying temperatures
The laying temperature must not be less than the specified minimum temperature of +4 C because the cable insulation and sheathing material will get brittle at low temperatures. When the temperature of the cables to be laid is less than + 4°C, the cables must be warmed up in a 20°C to 25°C warm room, such as a preheating tent, for about 36 to 48 hours, depending on the cable length. The cables may also be preheated by resistance heating of the cores by means of a transformer suitable for this purpose. But the limiting temperature of the conductor must not be exceeded with any heating method.
General
For fixed laying of lines (solid system of laying), types of lines intended for that purpose are to be used only.
The relevant type of line is to be selected depending on the place of laying.
Places of laying:
- dry and sometimes damp rooms,
- damp or wet rooms or outdoors,
- in soil,
- in water,
- flush or buried,
- on the surface, on trays and supporting brackets,
- on wood, cardboard, particle board, fibre board,
- with the possibility of direct contact of the line.
Laying problems
Lines, whether flush, buried or on the surface, are to be protected against mechanical damage not only during laying but especially under service conditions. Invisible lines should be laid vertically or horizontally to facilitate tracking of their course.
Mechanical protection
Uncovered lines, e.g. moisture-proof lines, must be protected by conduits at any points where mechanical damage may occur (breakthroughs in walls, ceilings/floors).
Heat accumulation
With the methods of laying in common use today, such as on trays, supporting brackets, in ducts and conduits, the lines are laid in bunches. In each line bunch (single or multi-wire) and in each closed duct, heat may accumulate. In order to prevent accumulation of heat, the current load factor for the respective type of laying is to be taken into consideration in the selection of the line cross sections.
Bending radii
In cable laying, when drawing off the cable from the cable drum and laying out the cable, e.g. with cable loops and cable connections the admissible bending radii are to be observed.
Table 22 Bending radii for power cables
Type of sheathing |
Laying Position |
Minimum bending radius |
Lead and aluminium sheathing |
during laying or bending |
20 d |
Plain aluminium sheathing |
during laying or bending |
25 d |
Plastic sheathing |
during laying or bending |
15 d |
Laying in soil
Laying of cables in the soil depends on the various different local conditions.
Table 23 Minimum laying depth with and without cable cover
Rated voltage |
Type of cable |
Dimensions Built-up ground with cover |
Ground not built-up with cover |
without cover |
|
- |
m |
m |
m |
up to 1000 V |
with concentric conductor or metal sheathing |
0.45(1) |
0.7(1) |
|
|
without concentric conductor or without metal sheathing |
0.45 |
0.7 |
1.0 |
more than 1 kV |
Compound-impregnated and plastic-insulated cables Oil-filled cables |
0.7 1.0 |
|
|
(1) Instead of the cover, warning tape is to be preferably used.
The minimum laying depth refers to the bottom edge of the top cable in one cable route. Laying depths of less than 0.7 m in public traffic areas are subject to the approval of the respective local authority.
Cables in cable trenches are to be arranged on a 10 cm thick coat of sand. Moreover, the cable is to be covered by another 10 cm thick coat of sand after laying. The top coat of sand is then to be covered by the cable protecting cover. The following cable protecting covers are in use:
- Cable protecting caps
It is to be ensured that the cable protecting caps covering the cable are filled with sand. Any cavity between the cable and the cable ducts will result in accumulation of heat which largely reduces the load-carrying capacity.
Figure 46. Cable protecting cover
with cable protecting caps - (1) correct application, (2) cavity between
protecting cap and cable
- Brick covers
Brick covers are low-cost protecting covers and enable quick and easy covering.
- Concrete covers
Instead of bricks, concrete slabs may be used. They should be generally used for laying of oil-filled cables.
Figure 47. Cable protecting cover
with concrete slabs and bricks - (1) with concrete slabs, (2) with bricks
- Cable conduits, moulded ducts
Cables run into buildings or under streets, rails and traffic-able ways require a high degree of mechanical protection. Conduits of clay, concrete or steel (not for single-conductor cables) are used for this purpose. If several cables are to be laid next to one another, moulded ducts are used.
Figure 48. Moulded duct
For the transition from the covering protection to the conduit it is to be made sure that the cable is not subjected to compressive or shearing stress.
- Cable layout in the soil
If several cables are laid in one cable trench, the lateral distance between the cables should be about 7 cm. Deviations are possible.
If high-voltage and low-voltage cables are laid in one cable trench, the high-voltage cables are to be laid deeper than the low-voltage cables.
Cable laying in the air
Cables should be circulated by air from all sides. Complete air circulation will not always be possible, e.g. in closed cable registers and laying of cables in ducts. In such cases a reduced load is to be calculated.
- Cable runs one upon the other High-voltage cables on the lower registers, low-voltage cables on the upper registers. Cables in ducts must not be laid on the bottom since the armouring would corrode in the event of intrusion of water. Cables intended for the protection, monitoring, control of plants or for transmission of information are to be laid separately from cables with rated voltages of more than 1 kV. Multi-conductor cables or cable systems with rated voltages of more than 1 kV should not be laid in layers one upon the other.
- Fixing of cables
Cables are to be fixed so as to prevent any deformation which is detrimental to the service properties. For cables on ceilings and walls it is also important to ensure good appearance.
Table 24 Distances for support and fixing of multi-conductor cables
Distances: in metres | |||
Metal-sheathed cables |
Plastic-insulated cables | ||
Support horizontal |
Fixing vertical |
Support horizontal |
Fixing vertical |
<1 |
<3 |
<1 |
<1 |
= |
= |
= |
= |
- Distances
A minimum distance of 2 cm between the cables and between the cable and the wall is to be maintained to prevent accumulation of heat in service.
Laying in water
Laying of cables through inland waters (e.g. rivers, lakes and channels)
Cables in the open sea are laid by specialized companies by means of laying ships.
- Types of laying
· Laying on the bottom of stagnant waters.
· Laying in a dredged channel.
· Laying in conduits - only in brooks, ditches and rivulets.
· Setting of cables or cable conduits into the water bottom.
- Type of cable
The cable must have a strong armouring and good protection against corrosion. Plastic covering or double protective covering of impregnated fibrous material (AA) is suitable for this purpose.
General
Conductors must be connected to machines and appliances, i.e. they must have an electrically conductive connection. A connection between conductors is also necessary. The connection must enable reliable flow of current from one conductor to the other one. That means, there must be good contact between the conductors at the joint.
Figure 49. Types of contact - 1 point
contact, 2 line contact, 3 surface contact
Type of connections (joints)
- Terminal connections:
· screw terminals,
· spring terminals,
· eccentric terminals,
· cone-type sleeve terminals.
- Plug-and-socket connections:
· appliance connectors,
· plug-in contacts.
- Wire-wrap connections.
- Soldered connections.
- Welded
connections.
- Pressed connections.
- Sliding connections (sliding
contacts).
Questions for recapitulation and testing
1. What are medium-voltage systems?
2. What is the difference
between open and closed systems?
3. What is the purpose of network system
coding to IEC 445?
4. What is the importance of the voltage in plant
engineering?
5. What are the effects of the intensity of current to be
transmitted on plant engineering?
6. What does the term distributing
plant mean?
7. How can the change of length of busbars caused by
heating be coped with?
8. What is the basic construction of a line?
9.
What is the basic construction of a cable?
10. What is the advantage of a
standard system of modular vessels for electrical engineering?
11. What types
of switching and distributing plants do you know?
12. What is the purpose of
switches?
13. What materials are insulators made of?
14. What is generally
to be taken into account in laying of lines and cables?
15. What is to be
ensured in cable laying with cable protecting caps?
16. What is the purpose
of electric
connections?