Back to Home Page of CD3WD Project or Back to list of CD3WD Publications

CLOSE THIS BOOKGeneration, Distribution, Use of Electric Current - Basic vocational knowledge (Institut für Berufliche Entwicklung, 141 p.)
4. Power transmission and distribution in power supply systems
VIEW THE DOCUMENT(introduction...)
VIEW THE DOCUMENT4.1. Types of networks
VIEW THE DOCUMENT4.2. International networks
4.3. Common voltage levels in the flow of electric energy
VIEW THE DOCUMENT4.3.1. The importance of the voltage
VIEW THE DOCUMENT4.3.2. Voltage levels of the elec-trotechnical networks
4.4. The importance of the electric current as dimensioning criterion for all transmission elements
VIEW THE DOCUMENT(introduction...)
VIEW THE DOCUMENT4.4.1. Operating current
VIEW THE DOCUMENT4.4.2. Short-circuit current
VIEW THE DOCUMENT4.4.3. Environment
VIEW THE DOCUMENT4.5. Common technical terms in the field of transmission and distribution
4.6. Lines and cables as transmission and distribution elements
VIEW THE DOCUMENT4.6.1. Basic terms
VIEW THE DOCUMENT4.6.2. Lines for heavy-current installations
VIEW THE DOCUMENT4.6.3. Power cables
4.7. Switching and distributing plants and accessories for the transmission and distribution of electric energy
VIEW THE DOCUMENT4.7.1. Switching and distributing plants
VIEW THE DOCUMENT4.7.2. Switches
VIEW THE DOCUMENT4.7.3. Accessories
VIEW THE DOCUMENT4.7.4. Insulating material (insulators)
4.8. Laying of lines and cables
VIEW THE DOCUMENT4.8.1. General
VIEW THE DOCUMENT4.8.2. Laying of lines
VIEW THE DOCUMENT4.8.3. Laying of cables
VIEW THE DOCUMENT4.8.4. Electric connections

Generation, Distribution, Use of Electric Current - Basic vocational knowledge (Institut für Berufliche Entwicklung, 141 p.)

4. Power transmission and distribution in power supply systems

Electric power system

The whole of electrotechnical installations and networks including all necessary additional devices for the generation, transmission and use of electric power within one regional unit,

Electrotechnical installation (or plant)

The whole of equipment required for proper functioning of the complete technological unit.

Electrotechnical network (or electric mains)

A system of interconnected electric lines of the same rated voltage for the transmission and distribution of electric power.

4.1. Types of networks

Supergrids (extra-high voltage systems)
(transmission function)
for power supply to larger areas with transmission voltages of 110 kV, 220 kV and 380 kV.

Medium-voltage systems
(distribution function) for power supply to smaller areas (towns, parts of towns, industrial plants, etc.) with transmission voltages of 1 to 30 kV.

Low-voltage systems (supply function) for power supply to the majority of consumers (electric household appliances and motors of low and medium capacity) with transmission voltages of up to 1 kV.

Open systems
have a single feeding point.

Closed systems
have two feeding points which makes the network more fail-safe.


Figure 7. Various types of networks as integral parts of the electric power transmission system - (1) supergrids (extra-high voltage systems (2) medium-voltage system (3) low-voltage systems - 1 mesh-operated network, 2 medium-voltage ring-operated network, 3 low-voltage distribution network (closed), 4 open network (multiple lump-loading), 5 star network, 6 feeding


Figure 8. Example of interconnected national networks - 1 transmission levels, 2 distribution levels, 3 international networks, - (1) power station, (2) heat-generating station, (3) industrial power station, (4) pumped storage power station

Table 2 Open and closed systems (networks)

Type and circuit


Advantages and disadvantages

Examples of application

Open systems with

end-loaded lines

simple circuit, clear arrangement, very simple protective system, very easy planning, good utilization, low costs, poor operational reliability, poor voltage maintenance, high losses

small industrial plants and local networks of small extent

multiple lump-loaded lines

branched lump-loaded lines

lighting installations




Closed systems with

lines with double feeding

simple circuit

local networks for long-distance settlements, extended factory halls

Closed system of

ring layout

clear arrangement

factory plants, medium-voltage distribution networks, higher-level supergrids

star layout

better voltage maintenance, less losses, easy planning, better operational reliability, poor utilization, acceptable costs, sophisticated protective system

low-voltage distribution networks in big industrial plants


meshed layout

very good operational reliability, very good voltage maintenance, low losses, very good utilization, less simple circuit, less clear arrangement, very sophisticated protective system, less easy planning, acceptable costs

local networks for bigger and large towns, low-voltage networks for big companies

4.2. International networks

The designation of networks and conductors is internationally coded to IEC 445.

The code letters used have the following meaning:

T terre (French) (earth)
I insulation
N neutral wire
C combined
S separated
P protection
E earth

TN-networks

Networks where one point of the network, i.e. one point of the service circuit, is directly earthed (T) and the casings of the equipment or installations are electrically connected with such point through a protective conductor (N). They apply the protective measures of connection to neutral or protective earthing with fault current return through metallic conductors (water pipes, cable sheathings).

- TN-C-network
PEN protective conductor with function of neutral wire.


Figure 9. TN-C-network

- TN-S-network
PE protective conductor carrying no operating current.


Figure 10. TN-S-network

- TN-C-S-network
PE protective conductor carrying no operating current.


Figure 11. TN-C-S-network

TT-networks

Networks where one point of the network is directly earthed (1) and the casings of the equipment or installations, irrespective of the existence of any neutral wire, are connected with earth leads which are not electrically connected to the earthed network point (T). Such networks, which are internationally called TT-networks, apply protective earthing (single earthing) using FI or FU protective circuits.

TT-network


Figure 12. TT-network

IT-networks

Networks where no point of the network is directly earthed (I) but the casings of the equipment or installations are directly earthed (T). Such networks apply the protective conductor system, protective earthing, FI and FU protective circuits.

IT-network


Figure 13. IT-network

4.3. Common voltage levels in the flow of electric energy

4.3.1. The importance of the voltage

The amount of voltage is decisive for the thickness of the insulation material (wire insulation) or the size of the distance of active conductors between each other and the earth. Economically this means the use of expensive or less expensive insulation material and, with respect to overhead lines, additionally occupation of ecologically important land. High-voltage overhead lines also involve overhead construction problems. Depending on the climatic zones, loads due to wind and ice, for example, are material-intensive design factors.

4.3.2. Voltage levels of the elec-trotechnical networks

The variety of the individual levels shall be demonstrated by means of an example of an installation


Figure 14. Example of possible voltage levels - 1 generator, 2 generator transformer, 3 substation transformer, 4 distribution transformer, 5 consumers, 6 voltages in kV

To enable efficient transmission of high powers over large distance, the transmission voltages have become higher and higher in the course of technological development.


Figure 15. Development of transmission voltages worldwide - 1 high-voltage three-phase transmission, 2 high-voltage D.C. transmission

4.4. The importance of the electric current as dimensioning criterion for all transmission elements

Having dealt with the effects of the voltage on the physical dimensions of all electrotechnical transmission elements, we now consider the effects of the electric current:

There are three objective factors of influence on the dimensioning.

4.4.1. Operating current

The operating current is important for normal operation which may be of continuous, short-time or intermittent type.

Continuous operation

Continuous operation means uninterrupted loading of all transmission elements by current of almost constant intensity which, depending on the current density, results in heating of the active conductors. That means that all materials and auxiliary materials (insulation) as well as components, which are in direct contact with the active conductor, absorb heat. The consequences are expansion and aging effects on busbars, metal-clad cables, wire insulations etc.

Short-time operation/intermittent operation

Short-time operation/intermittent operation mean that, after periods of heating, all transmission elements undergo periods of cooling. This may be aimed at maximum thermal peak-load on the one hand or at thermal load below the limit load on the other hand. It depends on the components to be used.

4.4.2. Short-circuit current

Faults normally involve extreme loads for all components, depending on the design of the installation in terms of protection:

- Instantaneous short-circuit current

The so-called instantaneous or asymmetric short-circuit current involves high electrodynamic loads for the installation parts immediately on its occurence. The intensive magnetic fields generated as a consequence of such current can physically destroy busbar installations, current transformer heads (insulator-type transformer), switching devices etc. Conductor elements of overhead lines may also be affected.

- Sustained short-circuit current

The sustained short-circuit current occuring after the instantaneous short-circuit current has several times the intensity of the operating current and, with a time lag after the short- circuit, results in heavy or extreme heating of all components in the fault circuit. Mostly such current destroys the installation parts unless this is prevented by adequate protective measures.

4.4.3. Environment

The thermal effects of the environment are important for the dimensioning of the installation with respect to the cross sections of the transmission elements and to the protective elements to be used. High ambient temperatures physically call for larger cross sections and low ambient temperatures permit smaller cross sections than normally specified for the operating current. Mutual heating is taken into account in installation engineering by providing for adequate distances of busbars, stranded conductors, lines and cables between each other and between components and for air circulation.

4.5. Common technical terms in the field of transmission and distribution

Outdoor plant/installation
Installation exposed to weather conditions without protection (see outdoor).

Open-type plant/installation
Installation with equipment not fully protected against accidental contact.

Outdoor(s)
Limited area in the open air featuring the same temperature and air humidity according to the local climate.

Assembly unit
A combination of several components or devices forming a functional unit.

Component
A single part that can only work in connection with other components.

Subassembly/module
Locally combined group of components which can function independently. Subassembly (in the context of a project) is a self-contained part of a plant/installation as defined from shipping and installation aspects.

Modular component/module
A component which, because of its specific modular design, can be assembled with other similar modular components into a consistent whole.

(Component) part
A constructionally and electrically self-contained member of a part of an installation.

Enclosed
Equipment and plants/installations which are protected against environmental influences.

Protected outdoor installation/plant
Outdoor installation which is protected against rainfall up to an angle of incidence of 30 degrees to the perpendicular.

Main distribution (system)
First distribution system after power feeding.

Information unit
The information unit of an installation or section or part of an installation comprises its locally functionally combined equipment for the generation, transmission, processing and reception of information, even though this is implemented according to the rules of heavy-current engineering.

Indoor installation/plant
Installation inside rooms or buildings.

Indoor(s)
Room in buildings which is free from effects of weather conditions

Mesh network
Closed network system consisting of crossing lines which are interconnected and fused at the crossing points. The crossing points are called “nodal points”, the closed sections between the nodal points a “mesh” and each part of the line “mesh line”.

Nodal point of a network
A point in the electric energy distribution system where more than two circuits (lines) can be interconnected.

Potential equalization
Electrically conductive connection between electrically inactive parts, such as water, gas and heater pipes, steel structures, metallic cable sheathings, foundation earth leads and protective conductors. This measure prevents a potential difference (voltage) between such parts.


Figure 16. Example of central potential equalization - 1 foundation earthing electrode, 2 heating tube system, 3 drinking water pipe, 4 gas distribution pipe, 5 house connection box, 6 customer’s meter. 7 potential equalization line (connection point optional), 8 potential equalization bar (if necessary), 9 water meter (conductively bridged, if the meter is built into a metallic pipe system), 10 structural design

Primary system

It serves the purpose of directly distributing the electric energy and includes all components directly involved in the transmission of electric energy.

(Main) busbar
A conductor - bar or rope - to which several conductors or lines are connected.

Busbar section
A portion of busbars or busbar systems.
Each section comprises only one part of the switchboard sections.

Busbar system
Busbars with connected switchboard sections.


Figure 17. Double busbar system - I system 1, II system 2

Busbar coupling
Conductive connection between busbar sections.


Figure 18. Longitudinal busbar coupling - I, II, III busbar sections

Switching plant

Distribution system with switching devices which make it possible to electrically connect and disconnect the outgoing main lines with/from the busbar.

Switchboard section
Local combination of the elements belonging to one branch.

Secondary system
It includes all facilities which are necessary for the protection, control, monitoring, measuring and metering but are not directly involved in the transmission of electric energy,

Station
Room or part of a building housing one or more electrotechnical installations or parts of installations and their service facilities for the purpose of distribution and conversion of electric energy.

Conversion
Change of the nominal value of physical quantities which are characteristic of the form of electric energy. Conversion includes transformation, frequency changing, rectification and inversion.

Subsidiary distributing system
Distribution system following the main distribution system.

Distribution plant
Electrotechnical installation including accessories, such as actuators, transformers, measuring devices etc., the main purpose of which is to distribute electric energy to several outgoing lines.

Cubicle (cell)
is a construction of suitable material which stands on the floor and has a degree of protection at least at one side but not at all sides.

4.6. Lines and cables as transmission and distribution elements

4.6.1. Basic terms

Lines
They serve the purpose of transmission and distribution of electric energy in general and of power supply and information trans-mision of any kind in particular. They are produced as bare (plain) and insulated types.

Cables
They have the same functions of energy transmission and distribution. Their particular construction permits their laying in the media air, soil and water under various external and internal conditions (mechanical, chemical, physical and electrotechnical).

System earthing and protective earthing wires
They include all conductors which carry off the electric energy to the earth in the event of fault. They have the potential of the earth. Since they have to be in direct contact with the soil, they are not insulated but have a high degree of protection against corrosion.

Types of laying

- Fixed laying
is a type of laying where the lines cannot change their position after installation (fixed with clips etc.)

- Movable laying
is a type of laying allowing the line to be frequently moved to another place (relocation of the equipment connected).

Line resistances


Figure 19. Equivalent connection diagram of a line - RLeit. line resistance, RIso insulation resistance, XL inductive reactance (inductance), XC capacitative reactacne (capacitance), Z consumer

- Ohmic line resistance RLeit

It depends on the length, material, cross section and temperature:

The conductor cross-section is to be selected so as not to exceed the admissible voltage and conduction loss:

- Insulation resistance RIso

It depends on the type of insulation, A general rule for cables and lines is

The insulation resistance is reduced by dirty surfaces, cracks in the insulation material, increasing tensional load and aging.

- Inductive reactance (inductance) XL

It depends on the line inductance and on the frequency:

The inductance per conductor depends on the length of the line “l”, the conductor distance “a” and the conductor radius “r”. It is calculated as follows:


L

1

a

r

H

km

mm

mm

If it is a line with return line, the total inductance of the line is to be calculated using 2.1 for the length. Because of the small conductor distance “a” of cables, the inductive reactance of cables is considerably lower than that of overhead lines.

Examples:

- Capacitive reactance (capacitance) XC

Capacitive charges occur between conductor and conductor and between conductor and earth.


Figure 20. Equivalent connection diagram of the capacitances of - a three-phase overhead line, CL conductor-conductor capacitance, CE conductor-earth capacitance

The mutual capacitance of a three-phase overhead line is calculated as follows:

CB =CE + 3 CL
CB= mutual capacitance
CE = conductor-earth capacitance
CL = conductor-conductor capacitance

Charge current of the three-phase line

The admissible values of capacitance and reactance are


Table 3 Influence of circuit elements on the behaviour of lines with respect to different types of voltage and current

Elements

Low voltage

Medium and high voltage

Direct current

Three-phase current

Line resistance

heating UV, PV

heating UV, PV

heating UV, PV

heating UV , PV

Insulation resistance

insulation and corona losses are low

insulation and corona losses increase with increasing voltage, therefore from 110 1<V bundle conductors for overhead lines

low corona losses

insulation between several conductors to be considered, e.g. in multi-conductor cables

Line inductance

self-inductance effects in the event of switching operations, little inductive phase shift since short line length

self-inductance effects in the event of load variations, inductive phase shift increases with increasing line length

self-inductance effects only when switching on and off

with 2 three-phase systems and operating currents flowing in opposite directions the self-inductance effects are compensated

Line capacitance

low

medium to high

capacitance increases with increasing line length and voltage

line capacitance depends on distance between each of the three conductors, on the insulation and screening

4.6.2. Lines for heavy-current installations

Bare (plain) lines

Bare lines are non-insulated conductors installed on insulating bodies (insulators), outside the area of contact on poles, behind protective grids or inside casings. As earth leads, bare lines are layed in the soil and in the area of contact.

- Bars (rails)

Solid, non-insulated conductors which, because of their shape or cross section, are highly resistant to deformation. They may be marked by colour codes.

Table 4 Bar (rail) sections and section moduli

No. Section

Position of conductor bars to each other

Section moduli

1 flat

high compared to 2

2 flat

low compared to 1

3 tubular

very high compared to 4

4 round

low compared to 3 and 1

5 channel

very high compared to 1 to 4

The bars are connected by welded or screwed connections.

They are held by line carriers on porcelain insulators or without carriers on thermoset plastic insulators or in hard paper fans.


Figure 21. Pin-type (rigid-type) insulator - 1 support, 2 bar carrier for two busbars (laid on edge)

Table 5 Hard paper boards for fixing of busbards

Designation

Construction

Comments

Hard paper fan

easy mounting

Hard paper fan with end strip

better hold compared to simple fan

Hard paper board with recesses

to be used where high bending stresses may occur (short circuit)

- Busbars

Busbars are bars or ropes to which several conductors or lines for current supply or derivation are connected. They are selected according to the current load (thermal load) from tables. Painted busbars can resist higher loads because the paint enables better dissipation of heat. The admissible D.C. load is higher than the A.C. load. Due to the skin effect of A.C. the cross section is not fully utilized. Therefore, pipe sections etc. are used in high-voltage installations. In order to avoid the accumulated temperature (ambient temperature V.. plus conductor temperature V,) to be exceeded, the admissible load current is to be reduced (load reduction) in the event of a higher ambient temperature. This can also be influenced by the way of laying.

Table 6 Cooling at flat section

Way of laying

Use

Cooling

On edge, horizontal

busbar current bar outlet

good

On edge, vertical

busbar

good

Flat, horizontal

current bar

very bad

Flat, vertical

outlet

good

Load because of temperature changes results in displacement of the busbars. Such temperature difference, which may be caused by varying heating effect of the current (alternating load) and by varying ambient temperature of busbars, results in change of length. Busbars are, therefore, fixed in line carriers which permit sliding and/or expansion joints are included in the course of the line. The slide supports and expansion joints make the expansion forces ineffective.


Figure 22. Diagram of busbar laying - 1 rigid support, 2 slide support, 3 expansion joint


Figure 23. Expansion joint - 1 expandable portion of a multitude of thin strips, 2 connection piece

Loads by heavy currents, such as in the event of short circuit, generate a heavy magnetic field around the conductor. Heavy forces may occur between the fields. Their effect depends on the instantaneous short-circuit current, supporting point distance, conductor section, type of laying and conductor distance.

- Current bars

Current bars are rigid conductors for the transmission of electric energy to portable devices through current collectors. They are used as series line in low-voltage and high-voltage installations. The main materials are half-hard rolled copper or aluminium.

Example:


Figure

- Earth leads

Earth leads are bare conductors lying in the soil with a firm an conductive connection with the soil.

The main materials for protective earthing and system earthing lines are:

· hot galvanized or copper clad strip steel or round steel with a minimum cross section of 50 mm,
· aluminium sections or rope with a minimum section of 35 mm,
· copper sections or rope with a minimum cross section of 16 mm,
· steel rope with a cross section of 120 mm ²

Table 7 Customary minimum cross sections of earth leads

Type of earth lead

Semi-finished products

Minimum cross sections/dimensions

Customary size

Strip earth conductors

strip steel

100 mm² min. thickness: 3 mm

30 mm x 4 mm 40 mm x 5 mm

round steel

diameter: 10 mm

diameter: 10 mm, 12 mm, 13 mm

Earth rods

mild steel tube angular steel or other similar sectional or round steel

diameter: 24 mm min. wall thickness: 3 mm 40 mm x 40 mm x 4 mm

diameter: 33.5 mm (1”) diameter: 60 mm (2”) 40 mm x 40 mm x 4 mm

Earth leads are interconnected by screwed, clamped and welded connections.

- Contact lines.

Contact lines are used for electromobiles with and without longitudinal carriers including safety stop cables. Conductors of sectional rails in workshops, on ceilings, under bridges, in tunnels and passages are also belonging to the contact lines.

Table 8 Contact lines, types and use

Designation

Material

Type of section

Purpose of use

Steel-copper contact line

Contact line with steel core and copper sheathing

No high resistance to wear, suitable for subsidiary routes with normal traffic and low speeds 1 copper sheathing 2 steel core 3 groove for fixing purposes

Copper contact wire

Solid copper section

as above but without steel core

Ri 80, Ri 100, Ri 120. use for standard-gauge railways

Steel contact line

All-steel contact line

For replacement purposes only, for short routes with little traffic

0 Steel current bar (rail)

Sectional steel rail with aluminium reinforcement

High resistance to wear, suitable for city or underground railway routes as feeder bar beside the track (only when provided with its own track bed - self-contained facilities) 1 steel rail section 2 aluminium subsequently or additionally added to enlarge the cross section 3 pick-up sides

Flat-section type

Copper or bronze

For small contact wires, crane tracks, conveyor equipment

Round-section type

Copper or copperbase alloys, bronze etc.

For crane equipment, conveyor equipment

- Overhead lines

These are open-type lines installed overhead in the open air with span lengths of normally more than 20m.

In order to place overhead lines out of reach of man and to ensure freedom of motion for vehicles of any kind, poles are required for overhead lines. Overhead lines of up to 1000 V, for example, are fixed on pin-type insulators or shackle insulators. Cap-and-pin insulators or long-rod insulators are used for rated voltages of more than 1000 V.


Figure 24. Types of poles - (1) supporting pole (straight-line pole), e.g. wooden pole with reinforced concrete pole footing, (2) angle pole, e.g. wooden pole with anchor, (3) angle pole, e.g. wooden pole with tie, (4) terminal pole, e.g. wooden A-pole (anchor and terminal pole) 1 wooden pole, 2 reinforced concrete footing, 3 anchor, 4 tie


Figure 25. Pole head types - 1 use in the voltage range 0.4 to 6 kV as wooden pole or reinforced concrete pole, 2 use in the voltage range 6 to 20 kV as concrete pole (the central conductor is alternatingly run at the right-hand and left-hand side of the pole), 3 use for voltages of more than 20 kV up to about 220 kV as lattice steel pole


Figure 26. Insulators - 1, 2 pin-type (rigid-type) insulators, 3 shackle insulator, 4 cap-and-pin insulator, 5 long-rod insulator

- Open-type lines

Open-type lines include, for example, short connection lines in the area of buildings (over courtyards, between workshop halls etc.).

- Stranded conductors

Stranded conductors are multi-wire conductors which are movable because of their flexible construction.

- Earthing wires

Earthing wires are used to protect voltage-carrying conductors against direct lightning stroke or to carry off to the soil over-voltage of atmospheric or other origin and consequently to avoid or reduce step and contact voltages on poles and scaffoldings.

Marking of bare lines

Table 9 Identification colour codes for power transmission lines

Type of current

Conductor

Colour code

D.C.

L+

red

L-

blue

M

light-blue

Three-phase current

L 1

yellow

L 2

green

L 3

violet

N

light-blue

A.C.

L 1

yellow

L 2

violet

Table 10 Identification colour codes for protective earthing and system earthing lines

Type of earthing

Colour code

Protective earth

black

System earth

white with black cross-stripes

Joined protective earth and system earth

from the point of joining: black with white cross-stripes

Table 11 Identification colour codes for earthing lines from the conductor to the earth

Type of current

Conductor

Main colour

Identification colour additional colour as cross-stripes

Direct current

L+

black

red


L-


blue


M


white

Three-phase current

L 1


yellow


L 2


green


L 3


violet


N, PE


white


PEN


Single-phase A.C. to IEC

L 1

black

yellow


L 2


green

for raiIway facilities

L 1

yellow


L 3


violet

Two-phase A.C.

L 1

yellow


L 2


green

Insulated lines

- Construction

Insulated lines consist of a single insulated conductor or of multiple conductors insulated from each other and are provided with protection against impairment of the electric function. Normally they are not allowed for laying in soil and water.

· Conductor
Material: aluminium or copper, Type of conductor: single-wire, multi-wire or poly-wire, fine-wire or extra-fine wire.

Shape of cross section: round.

· Insulating
cover consisting of rubber, plastic material, glass silk or artificial silk.

· Sheathing
consisting of rubber or plastic material.

- Wire marking

The insulating covers of multi-wire lines are marked with a colour code for safety reasons and for quicker working.

· Protective conductor

Colour code of protective conductor: green-yellow,

The green-yellow wire may only be used as protective conductor or auxiliary earthing wire.

· · Multi-wire lines are produced with or without protective conductor

· · With flat lines, the wire with the relevant colour code is to be used as protective conductor.

· · Wire marking

Table 12 Wire marking

Number of wires

Lines with protective conductor

Lines without protective conductor

1

gnge

b1


b1

sw or br

sw or br

2

gnge sw (only for fixed laying)

b1 sw or br

3

gnge b1 sw or br

b1 sw br

4

gnge b1 sw br

b1 sw br sw

5

gnge b1 sw br sw

Gnge

green-yellow

br

brown

b1

blue

sw

black

- Abbreviations

All countries are aiming at standardized abbreviations for marking and identification. The following markings are an example:

· Group markings
A wire line
D triple line

F

flat line (ribbon conductor)

Fr

overhead line (wire or rope)

H

hose line

I

installation line (wiring line)

Kr

motorcar supply line

L

tubular lamp line

N

heavy-current line

P

testing and measuring line rubber-sheathed line for mines

X-ray line

S

special line

Sch

welding line

T

trailing line

TS

trailing line, multi-wire

TM

trailing line, single-wire

W

heater line

Z

twin line

ignition line

· Constructional elements

C

shield of metallic wires or conductive layer

CE

like C, but around each wire

G

insulating cover or sheathing of elastic material (rubber)

2G

insulating cover or sheathing of silicone rubber

GS

insulating cover, protective cover or fibre core of glass silk

St

control wire (St) shield of metal foil

T

carrying member

TX

textile fibre core

U

outer braiding

Ü

supervisory wire

Y

insulating cover or sheathing of PVC

2Y

insulating cover of polyethylene

· Additionally marked porperties of the line

fl

flat

h

increased electric strength

k

increased resistance to cold

1

specially light-resisting

ö

oil-resisting

öu

oil-resisting and non-inflammable

s

increased wall thickness

t

increased heat resistance

u

non-inflammable

· Additionally marked properties af the conductor

b

poly-wire

e

single-wire

f

fine-wire

m

multi-wire

m/v

multi-wire/compressed

vz

tin-plated

w

helical

z

increased tensile strength

· Colour code abbreviations

b1

blue

br

brown

dgn

dark-green

el

ivory

ge

yellow

gn

green

gnge

green-yellow

gr

grey

nf

natural-coloured

sw

black

ws

white


Figure 27. Insulated line - 1 sheathing, 2 insulating cover, 3 conductor


Table 13 Composition of abbreviations

- Insulated power lines for fixed laying - examples

· Lighting line

Abbreviation: NLZYF 2 x 0.5 - ws - (Un = 300/300 V). Fine-wire Cu-conductor, plastic (PVC) insulating covers. Both wires are in parallel. Preferential colour: white. Application: in and at lamps with fixed laying. For dry and sometimes damp rooms, in and at lamps.

· Plastic-insulated line

Abbreviation: NAYY-J 2 x 2.5 re - 1 kV - (Un =1 kV). Single-wire, round Al-conductor, plastic (PVC) insulating covers and sheathing with green-yellow wire. Universally applicable in all media for wiring and control purposes.

· Plastic-insulated wire line

Abbreviation: NY b 10 - bl - (Un = 300/300 V). Poly-wire Cu-conductor, plastic (PVC) insulating cover, wire line for protected laying (wiring). For installations, in and at machines, in cases of vibrations and frequent bending stress, in dry and sometimes damp rooms.

Table 14 Places of installation and examples of applications of insulated power lines for fixed laying

Type of line

Abbreviation

Rated 3) voltage

Application 2) Place of installation

Examples of applications

-

-

kV

1

2

3

4

5

6

7

8

--

Lighting line

NLZYF

0.3/0.3

x

-

-

-

-

-

-

-

in and at lamps

Tubular lamp line

NL2YY

7.5/7.6

x

-

-

-

-

-

-

-

advertisement illumination,

NL2YCY

7.5/7.5

x

x

-

-

x

x

x

x

particularly outdoors

Rubber-sheathed line









NIAGGöu

0.45/0.45

x

x

-

-

-

-

-

x

for illumination purposes

Silicone rubber- sheathed line

N2G

1 1)

x

-

-

-

-

-

-

x

in lamps, in and at thermic


N2Gf









appliances, in hot rooms

Installation lines

NIAZY

0.3/0.3

x

-

-

-

x

-

-

-

flush with intermediate ceiling installation

NIDAY

0.3/0.3

x

-

-

-

x

-

-

-

buried in bulk walls and ceilings and with underfloor and intermediate ceiling installation

Plastic-insulated cable

NYYD NYY

1

x

x

x

x

x

x

x

x

universally applicable for wiring and control purposes

NAYYd









NAYY









Plastic-sheathed line

NIYYf1

0.3/0.5

x

x

-

-

x

x

x

x

for wiring and control purposes


NIAYYf1









NILAYYf1









Plastic-insulated wire line

NY

0.3/0.3

x

-

-

-

-

-

-

-

for installations, in and at machines, in cases of vibrations or frequent bending stress


NYb










NAY










N2AY









Special-purpose

NSYb

0.6/1

x

-

-

-

-

-

-

-

for ships, rail vehicles

plastic-insulated

NSYf









wire line









Rubber-insulated

NGUb

0.6/1

x

-

-

-

-

-

-

-

rail vehicles

wire line

1.8/3









3.6/6









NGUf

0.6/1









1.2/2









special-purpose

NSGGföu

1.8/3

x

x

-

-

-

x

x

-

rail vehicles

rubber-insulated

NSGCGföu

and









wire line

NSGCGföuk

3.6/6









Explanations of the figures

1)
up to 1.5 square millimetres rated voltage 300/500 V
from 2.5 square millimetres rated voltage 450/750 V

2)
1 dry and sometimes damp rooms
2 damp or wet rooms or outdoors
3 in soil
4 in water
5 flush or buried
6 on the surface, on trays and supporting brackets
7 on wood, cardboard, particle board or fibreboan
8 when there is a possibility of direct contact of the line

3) Rated voltage indicated as conductor-earth voltage/conductor-conductor voltage

- Insulated power lines for portable equipment - examples

· Triple line

Abbreviation: NDY 3 x 0.75 - gr - (Un = 300/300 V). Fine-wire Cu-conductor, plastic (PVC) insulating cover. The three wires are in parallel. Colour: grey. For light portable devices (kitchen appliances, radio and TV sets), no thermic appliances and no extension line, in dry and sometimes damp rooms and when there is a possibility of direct contact of the line.

· Light plastic hose line

Abbreviation: NHYY1 3 x 0.75 - gr - (Un = 300/300 V). Fine-wire Cu-conductor, plastic (PVC) insulating covers and sheathing. Colour of sheathing: grey. For office machines, vacuum cleaners, refrigerators, in dry and sometimes damp rooms and when there is a possibility of direct contact of the line.

· Medium shielded plastic hose line Abbreviation: NHYYCY 3 x 1 - gr - (Un = 300/500 V). Fine-wire Cu-conductor, plastic (PVC) insulating covers, inner and outer sheathing. Shield of Cu-wire mesh. Colour of sheathing: grey. For medium mechanical stress, extension lines, shielding electric fields, for control purposes, in dry and wet rooms, in the open air, in water, on wood, cardboard, particle board and fibreboard and when there is a possibility of direct contact of the line.

Table 15 Places of installation and examples of applications of insulated power lines for portable equipment

Type of line

Abbreviation

Rated voltage

Application Place of installation

Examples of applications

-

-

kV

1

2

3

4

5

6

7

8

-

Twin line











light portable devices,

Triple line

NZY

0.3/0.3

x

-

-

-

-

-

-

x

no thermic appliances and extension lines

Plastic hose lines: especially light light

NDY

0.3/0.3

x

-

-

-

-

-

-

x


NHYY11

0.3/0.3

x

-

-

-

-

-

-

x


NHYY1

0.3/0.3

x

-

-

-

-

-

-

x

office machines, vacuum

NHYY1f1









cleaners, refrigerators

medium

NHYY

0.3/0.5

x

x

-

x

-

-

x

x

for medium mechanical stress, extension lines

medium shielded

NHYYCY

0.3/0.5

x

x

-

x

-

-

x

x

like NHYY, shielding of electrical fields, for control purposes

with supporting facilities

NHT2YY

0.3/0.5

x

x

-

-

-

x

x

x

for high tensile stresses, such as

with supporting facilities and shielded

NHT2YCY

0.3/0.5

x

x

-

-

-

x

x

x

elevators/lifts

Rubber hose lines: with textile braiding

NHGGU1

0.3/0.3

x

-

-

-

-

-

-

x

light thermic appliances, electrothermic appliances, extension lines

light

NHGG1

0.3/0.5

x

-

-

-

-

-

-

x

for medium mechanical stresses, workshop devices, tools, also outdoors, agricultural imple ments

Rubber hose lines: heavy





1)





NSH

0.6/1

x

x

-

x

-

x

x

x

for higher mechanical stresses,

NSHöu









construction machinery, heavy

NSHöuk









workshop equipment

NSHCk





1)




heavy with sup porting facili ties

NSHT

0.45/0.75

x

x

-

x

-

x

x

x

for high tensile stress (control purposes in shafts and on hoist ing gears)


NSHTöu










Rubber hose lines for mines





1)




for underground mines, in pits


NOö

0.6/1

x

x

-

x

-

x

x

x

with firedamp and explosion hazards

with supervisory conductor

NQÜö

0.45/0.75

x

x

-

x

-

x

x

x

like NQö but with supervisory

Welding line

NSCHGöu

0.12/0.2

x

x

-

-

-

x

-

x

interconnection line between transformer and electrode holder

Trailing line





1)




single-wire

NTM

1.8/3

x

x

-

x

-

x

x

x

for high mechanical stress, con

NTMöu

3.6/6









nection of high-voltage motors

NTMCöu

12/20









and power supply installations

NTMCöuk

18/30





1)




(peak-load stations)

four-wire

NTSCEöu

3.6/6

x

x

-

x

-

x

x

x

as above, power supply for big

6/10









equipment (excavators and

NTSCEöuk

12/20









conveyor bridges in open-cast

18/30









lignite mines)

1) except in mining, on building sites and for portable equipment

- Fabricated power lines - examples

These are industrial, standard lines with integral connectors.

· Mains connection lines

· · Abbreviation: A1-2-32/7 - gr -

Mains connection line (A1) with integral coupler plug, two-pin, 2.5 A (also called

European plug) for appliances of protection class II. Line: NZY 2 x 0.75 mm, length 2 m, dismantling length 32 mm, insulation-stripping length 7 mm. Colour: grey.

Application: mains connection of electrical appliances of up to I = 2.5 A. Not allowed in the open air and in wet rooms.


Figure 28. Mains connection line with integral coupler plus 2.5 A

· · Abbreviation: EHI-4-63/7 - sw -

Mains connection line (EHI) with integral safety plug, 10/16 A, of plastic material and with increased degree of protection for appliances of protection class I. Line: NMH 3x1 mm2, length 4 m. dismantling length 64 mm, insulation-stripping length 7 mm.

Colour: black. Application: mains connection of electrical appliances of up to In = 16 A.

Allowed in the open air and in wet rooms.


Figure 29. Mains connection line with integral safety plug 10/16 A

· Interconnection lines

Abbreviation: 22-1, 6-3-32/7 - sw -Interconnection line (Z2) with integral appliance lead-in of type 3 at one end. Line length: 1.6 m. Dismantling length 32 mm. Insulation-stripping length 7 mm. Colour: black. Application: interconnection line with fixed connection at both ends.


Figure 30. Interconnection line with fixed connection at both ends - 1 with integral appliance lead-in, 2 with outer braiding

- Not allowed laying of insulated lines


Table 16 Not allowed laying of lines carrying voltage in operation

4.6.3. Power cables


Figure 31. Power cable - 1 conductor, 2 conductor insulation, 3 belt, 4 sheathing, 5 inner protective covering, 6 armouring, 7 outer protective covering

Construction

Cables consist of one or more insulated electric conductors. They are provided with one or more protective layers with properties allowing the cables to be laid in cable trenches, cement ducts or cable ducts and water without impairing the electric function.

(The cable construction is always considered from inside to outside)

Constructional elements

- Conductor
Material: aluminium or copper.
Type of conductor: single-wire or multi-wire.
Shape of cross section: round, oval, sector-type.

- Conductor insulation
Insulating cover may be made of

· polyvinyl chloride (PVC), for rated voltage 1 kV,
· polyethylene (PE), for rated voltage up to 30 kV,
· paper, well impregnated with cable impregnating compound up to 30 kV, impregnated with cable oil up to 380 kV (internationally)

- Core

Conductor with insulating cover.

- Belt

Paper insulation, well impregnated with cable impregnating compound, in several layers enclosing the core as additional insulation.

- Sheathing

Seamless lead, aluminium or plastic covering, protects the interior of the cable from external mechanical and chemical effects.

- Inner protective covering

Bitumen-impregnated paper layers with fluid intermediate bituminous compound which, in the event of mechanical stress (such as bending of the cable), permit pressure compensation between the metal sheathing or plastic sheathing and the cable armour.

- Armour

Material: steel.

Type: 2 layers of strip steel with protective coating against corrosion or round-wire armour, non-magnetized.

Type of wrapping: closed or open (round-wire armouring).

25 % overlapped (strip-steel armouring) and, against special order, anti-twist wrapping.

- Outer protective covering

Single protective covering of coarse tow yarn or textile tape with semifluid compound and non-sticking coating - A, double protective covering as above - AA, protective covering of PVC - Y. Cables with protective covering of impregnated fibre materials are allowed in rooms if impregnated against inflammability.

Classification

- Purpose

· control purposes,
· transmission of electric power.

- Voltage

· low voltage: ³ 42 V ‘= 1 kV
(£ 42 V low voltage)

· high voltage: medium voltage 1 to 30 kV.
extra-high voltage 110 kV.

- Construction

· compound-impregnated cable,
· plastic-insulated cable,
· oil-filled cable for extra-high voltages,
· special-purpose cable,
· plastic-insulated cable with more than five cores.

Wire marking

- Purpose

Marking of the wires largely precludes that the wires get mixed up and. therefore, is in the interest of higher reliability of service and easier installation.

Wire marking is not necessary for cable of more than 1 kV.

Up to 1 kV the wire marking corresponds, to a large extent, to that of lines. The marking of the protective conductor is of special importance.

The green-yellow wires are to be used as protective conductors.

- Type of wire marking

For the benefit of unmistakable definition of the type of wire marking (especially where two types are possible) of a multi-wire 1 kV cable, the letter code has been extended to include 3 and 0.

Examples:

NAYY-J 4 x 25 re 1 kV four-wire plastic-insulated NAYY cable with a wire marked green-yellow or with figure code 3-1-2-3.

NAYY-0 4 x 10 re 1 kV four-wire plastic-insulated NAYY cable with a nominal conductor cross section of up to 50 mm and the colour code gnge/b1/sw/br or with figure code 1-2-3-4.

NAYY 1 x 185 sm 1 kV
single-wire plastic-insulated NAYY cable.
Table: Wire marking of 1 kV cables

Table 17 Wire marking of 1 kV cables



Wire marking

Type of cable

by colours

by figures, colours or letters



cables with green-yellow wire (letter “J”)

cables without green-yellow wire (letter “O”)

cables with a green-yellow wire or with a wire marked with the letter J (letter “J)

cables without a green-yellow wire or without a wire marked with the letter 3 (letter “O”)

(1)

(2)

(3)

(4)

(5)

Compound-impregnated cables

single-wire

nf or sw

-

-

or plastic-insulated cable

two-wire

gnge/nf or
gnge/sw

-

J-1

-

more than 35 mm2

three-wire (also cables with concentric conductor or Al sheathing

-

nf/nf/nf or
sw/sw/sw

-

1-2-3

four-wire

gnge/nf/nf/nf or gnge/sw/sw/sw

nf/nf/nf/nf or sw/sw/sw/sw

3-1-2-3

1-2-3-4

NYY, NAYY, NYYd,
NAYYd with a conductor cross section up to 2 35 mm²

two-wire three-wire four-wire five-wire

gnge/sw
gnge/b1/sw
gnge/b1/sw/br
gnge/b1/sw/br/sw

b1/sw
b1/sw/br
b1/sw/sw/br
b1/sw/br/sw/sw

gnge-1
gnge-1-2
gnge-1-2-3
gnge-1-2-3 -4

1-2
1-2-3
1-2-3-4
1-2-3-4-5

Plastic-insulated cables

(2) direction wire in the outer stranding layer

gnge

br

gnge

-

with more than 5 wires

marked wire in each stranding layer

b1

b1

1 to 36(1)

1 to 37(1)

other wires

nf or sw

nf or sw

b1 blue, br brown, gnge green-yellow (for compound-impregnated cables green-natural-coloured), nf natural-coloured, sw black

(l) Sequence of figures 1 to 37 from inside to outside
(2) Seven-wire plastic-insulated cables have one gnge-wire, plastic-insulated cables with more than 7 wires do not have a gnge-wire. Deviations are possible.

Note: When using the gnge wire marking, one of these colours should cover not less than 30 % and not more than 70 % of the wire surface of each 15 mm long wire portion,

Cable designation

To get clear and full information of the specific technical construction of a cable and to avoid extensive description, standardized abbreviations for cables are also aimed at. The following markings shall also serve as an example:

- Insulating cover

Y PVC insulating cover
2Y PE insulating cover
O oil insulation

- Shield

H shield of wire

- Concentric conductor

For 1 kV cables with an electrically effective cross section of

Fa

flat-wire aluminium

Fu

flat-wire copper

Ra

round-wire aluminium

Ru

round-wire copper

For

1 kV cables with an electrically effective cross section of

Ca

aluminium

Cu

copper

- Sheathing

K

lead sheathing

Ka

aluminium sheathing

Y

PVC sheathing

- Armour

B

strip-steel armouring

Ba

aluminium armouring

BY

rigid-PVC armouring

R

round-wire steel armouring

G

anti-twist steel armouring

- Protective covering

A

single protective covering

AA

double protective covering

Y

PVC protective covering

- Protection against corrosion

· K

single protection

· KK

double protection

(Letter is omitted for cables with sheathing or concentric conductors of aluminium.)

- Types of conductors

e

single-wire

m

multi-wire

r

round

s

sector-type

- Additional marking of constructional elements

o

open-type armouring, e.g. Ro

w

corrugated constructional element Kaw

z

hardening additive Kz

v

cross-linke

d

2Yv d twist-marked Yyd

- 1 kV cables

J

with green-yellow wire or with wire figure

0

without green-yellow wire or without wire figure 0

- Examples

NYKY

plastic-insulated cable with Cu-conductors, lead sheathing and plastic protective covering

NAYKY

plastic-insulated cable with Al-conductors, lead sheathing and plastic protective covering

NAYY

plastic-insulated cable with Al-conductors and plastic sheathing

NAKY

paper-insulated compound-impregnated cable with Al-conductors, lead sheathing and plastic protective covering

···· A

outer protective covering of coarse tow yarn or textile tape with semifluid compound and non-sticking coating

··· Y

with outer protective covering of PVC

··· BA

with strip-steel armouring and outer protective covering of coarse tow yarn or textile tape

··· RoA

with open-type round-wire steel armouring and outer protective covering of coarse tow yarn or textile tape

··· RG

with anti-twist round-wire steel armouring

NY2YHCaY

polyethylene-insulated cable with wire shields, concentric conductor of aluminium strips and flat-wire aluminium, PVC sheathing

Note:

In the case of copper conductors the A is omitted after the N in the abbreviation.

Manufacturing types

- Compound-impregnated cables

Paper-insulated power cables. Single-wire or multi-wire low-voltage or high-voltage cables with compound-impregnated or compound-impregnated and drained paper insulation. They may have a metal sheathing cladding all or individual wires and, in addition, special protective coverings, depending on the purpose of use.

- Belted cables

The simplest cable from the manufacturing point of view. They are produced with three or four wires.

· Properties

The poor thermal conductivity of the belt increases the heating of the cable. The impregnation compound presses outwards, cavities are formed inside. Increasing danger of glow discharge, enhanced by increased rated voltage.

· Use

In installations with rated voltages of up to 10 kV.

- Hoechstaedter cables (H-type cables)

Cables with individual shielding of the wires, without belt.

· Properties

The mutual contact of the wire shielding and metal sheathing (electrically conductive) restricts the electric fields to the wire insulation

· Use

In installations with rated voltages of up to 30 kV.

- Single-conductor cable

Differs from the normal construction of cables. Expensive manufacture.

· Properties

Good thermal conductivity, thus higher current-carrying capacity; high short-circuit strength (When laid on cable trays, registers etc. and on cable lifting points at terminal boxes, special measures of fixing of the cables may be required in view of the high dynamic effects of possible short-circuit currents); easy instal-lation and repair. Higher additional losses because of magnetic fields inside the cables and of mutual magnetic influence of several cables (three-phase systems)

· Use

In D.C. and three-phase installations of any rated voltage.

- Separate lead type cables (SL-type cables)

Combination of three single-conductor cables - without pressure protection and armouring - into one cable.

· Properties

The greater mass of metal (metal sheathings) results in better thermal conductivity, thus good electric shielding of the conductors against each other, reduction of losses.

· Use

In 20 kV and 30 kV installations.

- Plastic-insulated cables

Plastic-insulated cables are cables with plastic material used as insulating, filling and sheathing materials.

· Advantages compared to compound-impregnated cables The costs of manufacturing and processing of plastic-insulated cables are considerably lower than those of conventional cable manufacture and processing. Advantages include: considerably smaller mass, better colour coding, higher elasticity and easier processing.

· Use

In installations with rated voltages of up to 30 kV.

· Types

Cables with plastic-insulated cores and plastic inner sheathing, armouring and outer covering, such as NAYBY.

Cables with plastic-insulated cores, concentric outer conductor and plastic outer sheathing, such as NAYFaY.

The various plastic coverings are chemically composed according to the relevant purpose, i.e. sole purpose of insulation (dielectric strength, core insulation), sole purpose of filling (filling of cavities, filler material) as well as purposes of protection against chemical and mechanical influences (outer sheathing)

· Polyethylene (PE) proved to be particularly suitable as raw material for core insulations and sheathings.

- Special-purpose cables

This term covers all cables for special purposes of use:

· Power cables for ships NMYCY.
· Aerial cables NLAYYT, NLA2YvHCaeYT.
· Radiation-proof cables NXGG.-

Such cables are exposed to extraordinary conditions at the place of installation, such as high thermal and chemical as well as extreme mechanical stresses.

- Plastic-insulated cables for control and information purposes They differ from power cables by a higher number of cores (7 to 37 cores) and a cross section ranging from 1.0 to 6.0 mm Cu and 2 2.5 to 6.0 mm Al. They are produced as plastic-insulated cables.

· Properties

Special colour code and a specific way of counting the cores.

Compared to multi-conductor cables of the same cross section, the load on the cores is considerably lower because of the very poor heat dissipation (massing of cores).

· Use

Such cables are generally produced up to a rated voltage of 1 kV only and used in heavy-current installations for measuring, signalling and control purposes.

4.7. Switching and distributing plants and accessories for the transmission and distribution of electric energy

4.7.1. Switching and distributing plants

Standard system of modular vessels

It is a modern system of modules that can be universally combined and be used in electrical and electronic engineering. Such a system enables a high packaging density in electrical installations/plants.

The vessels serve for covering and/or housing of components, modules, subassemblies, units and devices. The vessels can be classified in groups of order.

- Zeroth order vessels

Circuit cards, card plug-in units (non-protected), card inserts (non-protected)

Use:

The assembled printed circuit boards of standard sizes including plug-and-socket-connectors or terminal connectors are intended for use in vessels of 1st or 2nd order.

- First order vessels

Plug-in units and card inserts (protected), card plug-in units and card inserts (shielded), rack plug-in modules, rack inserts. Use:

As complete modules, mostly as self-contained functional units.

- Second order vessels

Sub-racks, plug-in subassemblies, subassembly inserts, card inserts.

Use:

As rigidly built-in or plug-in units they are used, for example, to complete the tiers in a cabinet. Together with the zeroth order vessels they fulfil the mechanical functions.

- Third order vessels

Built-in vessels, mounting vessels, box-type vessels, panel vessels, racks, cabinets, outdoor cabinets, control-room cubicles, consoles, desks.

Use:

They are the outer enclosure of the final product and have a decisive influence on the degree of protection, climatic class etc. Besides the front panels, they determine the shape of the final product. In connection with the 2nd order vessels they ensure the mechanical functions.

- Fourth order vessels

Subcarriers, plug-in unit carriers, insert carriers, mounting racks, swing-out racks.


Figure 32. System structure of indoor switching plants using the standard system of modular vessels (1.1 switchboard section. 2.2 contactor section, 1.3 capacitor section, e.g. of 400 mm mounting depth), (2.1 switchboard section, 2.2 contactor section, 2.3 capacitor section, e.g. of 800 mm mounting depth), 3 subsidiary distribution, 4 energy distribution, 5 transformer box, 6 peak-load centre, 7 busbar module, 8 structural head of an indoor switching plant

Indoor switching plants

- Use

Switchboard sections, contactor sections and capacitor sections are intended for universal use as main and subsidiary distributions. All sections of the same mounting depth can be combined with each other. The sections of 800 mm mounting depth can be combined with transformer boxes into peak-load centres (see also Fig. 32).

- Construction

Each section has a busbar chamber, an equipment chamber and a cable termination and current bar chamber to connect the equipment modules.

- Equipment modules

Plug-in sub-units, plug-in units or inserts to be mounted in the sections. Plug-in units are connected through plug contacts, inserts are rigidly built in and connected.

- Sections

The different sections are:

· Switchboard sections with on-load switches, power circuit breakers, fuses, contactors, no-load switches, relay modules for information processing.

· Contactor sections with contactor outlets for various circuits and rated currents.

· Capacitor sections with capacitors for power-factor compensation.

· Electric power distributors with power switches, NH-fuse outlets, break-jack points, busbars and/or combinations for use in power supply substations.

· Subsidiary distributions with current-limiting power switches, on-load switches and fuses.

· Transformer boxes with dry-type transformers up to 1000 kVA.


Figure 33. Front view of an indoor switching plant as peak-load centre (example)

Sheet steel-enclosed low-voltage distributing plants (SLD system)

The SLD system offers a variety of possible combinations with a minimum number of component parts.

- Construction

Sheet steel enclosure of standard size to house switchgear, transducers, meters, measuring instruments, transformers, pushbutton switches, signal devices and busbars. The assembled complete distributions are mounted on supporting racks.

- Use

Wherever electrical devices are to be protected against moisture, dust and mechanical damage. They are particularly suitable for industrial, mining and metallurgical operations and building sites.


Figure 34. SLD mounted on supporting rack with connection lines


Figure 35. Example of a specifically assembled SLD - 1 general connection diagram, 2 assembly of casings

Standard Box System (SBS)

A metal (aluminium alloy) or plastic box with the relevant components already mounted by the manufacturer.

- Construction

Table 18 Metal type SBS for IP54 and partly for IP56

Empty boxes

Appliance boxes

Accessories

Screw caps (5 sizes)

Juntion boxes

Cable terminal boxes


Fuse boxes

Flanged caps


Barrier boxes

Insert bowls

Screw caps (4 sizes)

Switches

Sealing sheets


Terminal boxes

Potential equalization rails


Repair switch boxes

Quick-seal couplings


Ballasts

Protective conductor rails



Special accessories

Table 19 Plastic type SBS for IP 54

Empty boxes

Appliance boxes

Accessories

Screw caps (3 sizes)

Junction boxes

Cable terminal boxes


Fuse boxes

Insert bowls


Barrier boxes

Sealing sheets


Terminal boxes

Protective conductor rails


Base-mounted sockets



FDSP, 16 A


- Use

· Plastic boxes are only used in installations/plants with temperatures up to 60°C. They are very corrosion-resistant.

· Metal boxes are universally applicable under extreme conditions. The IP 56 version is mainly intended for use in shipbuilding.

Low-voltage cabinet distributing system (LCD system)

- Construction

Sheet steel enclosure with mounting frame

The mounting frame serves for fixing of the devices and for holding of the device covers. After mounting and wiring it is bolted in the cabinet.

Cabinet distributors can be provided with D-fuse sockets up to B33, NH-fuse sockets up to size 1, gang switches up to 25 A, cam switches up to 100 A, air-break contactors up to IDS, motor protection switches, adapting transformers, automatic cut-outs and meter boards.

- Use

LCD systems are used in housing and social building construction, in industry and agriculture.


Figure 36. Example of a central house connection box


Figure 37. Example of a distributing cabinet for a house wiring system

Outdoor switching and distributing cabinets

Cabinets for switching purposes and distribution of electric energy, e.g. for use in the building industry, in traffic engineering, rail-way facilities, street lighting, agriculture, on building sites.


Figure 38. Example of a cable terminal box 1 equipment support

Medium-voltage switching stations, substations and transformer stations

- Switchgear cubicles (cells)

Of metal-enclosed or open (solid insulation) type, they are used as line and on-load switch cubicles, cable and measuring cubicles in switching stations for industrial power supply (metal-enclosed types) or in closed electrotechnical rooms, particularly for switching of transformers, and on heavy open-cast mining equipment (solid insulation).

Table 20 Technical data of switchgear cubicles

Switchgear cubicle

Insulation voltage

Rated current

Metal-enclosed type

12 kV


1250 A



or 2500 A

Solid insulation type

36 kV


1250 A

- Substations

Buildings mostly constructed from industrially prefabricated assemblies, brickwork or concrete. They serve to transmit the electric energy through cables to the medium-voltage and low-voltage levels. They have separate medium-voltage and low-voltage chambers.


Figure 39. Example of the layout of a substation with cable connections - 1 cable entries/exits, 2 transformer chamber, 3 low-voltage switching plant chamber, 4 medium-voltage switching plant chamber

· Equipment

· · Medium-voltage switching plant 6 and 10 kV with semi-open or sheet steel-enclosed switchgear cubicles 15 and 20 kW with sheet steel-enclosed switchgear cubicles 30 kV with solid-insulation switchboard sections

· · Low-voltage switching plant with indoor switching equipment having the following purposes or functions: connection of oil-filled transformers up to 1600 kVa, station service distribution, emergency power plant (accumulators), measuring processes, connection to earth, lighting installations.

- Transformer stations

Cable stations, overhead-line stations, pole stations and outdoor stations.

· Cable stations

Buildings of brickwork, concrete or industrially prefabricated assemblies. They are used as local network stations and for small or medium industrial plants.


Figure 40. Example of a local network transformer station (layout) 1 transformer, 2 indoor switching plant, 3 switchgear cells. 4 relays, 5 accessories

· Overhead-line stations Buildings like cable stations. They are used as terminal station or through-station for local networks and smaller industrial plants.


Figure 41. Example of an overhead-line through-station - (1) schematic circuit, (2) external view

· Pole stations

Transformers up to 160 kVA are erected on a platform at the overhead-line pole. They are used for overhead line systems in thinly populated areas with low power consumption.

· Outdoor stations

Transformer stations for temporary supply of electric energy for building sites, mining projects, mass events etc.

They are enclosed and can be moved on skids or wheels.


Figure 42. Schematic drawing of an enclosed outdoor station on skids - 1 medium-voltage switching plant, 2 transformer, 3 low-voltage switching plant

4.7.2. Switches

General

Switches are devices to open (break) and close (snake) current paths with all parts necessary for connecting or disconnecting firmly mounted on a joint base.

The force necessary for changing the switch position (ON/OFF) is provided by switch drives, such as

- hand drive
- magnet drive
- motor drive
- compressed-air drive

Low-voltage switches

The following types are in use:

- No-load switches

They must only be switched without load.

- On-load switches

They are designed for switching under load. Different types are:

· Installation (or house-wiring) switches

On-load switches designed for low-voltage electrical installations in rooms of residental buildings, industrial buildings and annexed buildings.

They are designed for a rated voltage of 250 V and for rated currents of 6 A and 10 A. They are classified according to

· · the mode of switching (e.g. cut-out switch, two-way switch, intermediate switch), the mode of driving (e.g. toggle switch, rocker switch, rotary switch, push-button switch),

· · the type of installation (surface switch, flush switch, appliance switch),

· · the place of installation (e.g. moisture-proof switch, explosion-proof switch).

· Remote-controlled installation switches

Electromagnetic switches controlled by a low voltage of 12 V or by 220 V

· They are used in residental and social buildings.

- Overload circuit breakers

They are mainly used as motor switches to master high starting currents. They are tested by 10 to 20 times the rated current. Different types are:

· packet cam-operated switches,
· contactors,
· thermal relays,
· vacuum contactors,
· current-limiting power switches.

High-voltage switches

The following types are in use:

- Disconnectors.
- Load-break switches.
- Power switches.

4.7.3. Accessories

For bare lines

- Holders:

insulated supports,
line-supporting fans or plates,
low-voltage and high-voltage overhead-line insulators,
bushing insulators.

- Line poles:

straight-line poles,
angle poles with anchors or ties,
terminal poles,
wooden poles,
reinforced concrete poles,
lattice steel poles.

- Conductor joints:

crimp joints,
screw and rivet joints,
cone joints,
seam joints,
jointing links,
jointing sleeves,
weld joints.

For insulated lines

- Holders:

clips (single and multiple types, nail, screw, louvre, spacer, series clips, anchor logs, register clips, single-tab and double-tab, with wall bolt),
supporting straps,
conduits,
duct systems,
surface sypes,
buried types,
bracing wire.

- Branch boxes, conduit boxes, switch boxes.

- Switches, sockets.

- Lighting fittings.

- Meter boards.

- Distributions.

For power cables

- Terminal boxes (sealing ends)

· For plastic-insulated cables:

wrapping terminations (indoors),
cast-resin terminations (outdoors).
slip-on and casing terminations (indoors and outdoors).

· For compound-impregnated cables:

cast-resin terminations (indoors),
hose terminations (indoors),
casing terminations (indoors and outdoors).

- Multiple-joint boxes:

For distribution of the individual cable cores of multi-core cables with joint sheathing.

Installation only in connection with single-conductor terminal boxes.


Figure 43. Multiple-joint box 1 multiple-joint box, 2 metal conduit. 3 single-conductor terminal box

- Distribution clips:

For distribution of separate lead type cables with each cable core with sheathing ending in a single-conductor terminal box.


Figure 44. Distribution clip (end clip) 1 end clip, 2 metal sheathing, 3 single-conductor terminal box

- Cable sleeves.

- Compensation tanks:

For compensation of the quantity of the impregnation compound in compound-impregnated cable installations or for compensation of the oil pressure in oil-filled cables or oil-filled cable installations.


Figure 45. Example of a compound compensation tank arrangement 1 connecting piece, 2 formed bend, 3 joining piece, 4 joining T-piece, 5 connecting branch, 6 compound compensation tank. 7 minimum level of compensation tank, 8 single-conductor terminal boxes, 9 single-conductor or separate lead type cables, 10 multiple-joint box. 11 three conductor cable

4.7.4. Insulating material (insulators)

Purpose

Insulators shall insulate current-carrying electric conductors with respect to other conductive parts which are not intended for current conduction.

Materials

- Porcelain is the material mostly used. It is age-resistant, corrosion-resistant, has a high mechanical strength and is a good insulator. Porcelain is used for indoor and outdoor low-voltage and high-voltage installations.

- Thermoset plastic material is non-corrosive, has a high mechanical strength and is a good insulator but it is aging and temperature-sensitive.

- Hard paper (laminated paper) has a high mechanical strength, is a good insulator but sensitive to moisture and aging. Thermoset plastic material and hard paper are only used for indoor low-voltage installations.

Stress

- Electric stress

The insulators must be designed so as to preclude breakdown or spark-over from the electric conductor to parts of the installation which are not belonging to the electric circuit. Moisture and dirt deposit are favourable for voltage spark-over.

- Mechanical stress

The insulators in overhead-line installations are subjected to tensile stress to all sides. The tensile stress is constantly varying, depending on the weather conditions (e.g. wind, hoar-frost, temperature variations) and the effects of electromagnetic forces between the conductors. In indoor installations there is mechanical stress only by electromagnetic effects between the conductors, i.e. by cantilever force and short-circuit force.

- Thermal stress

Temperature variations in the environment and in the lines have effects on the fastening elements between the conductor and insulator. Different heat conductivity and expansion coefficients result in mechanical stress which, in extreme cases, can destroy the insulator.

4.8. Laying of lines and cables

4.8.1. General

Damage to the conductor or insulator of any line or cable may occur as a result of improper transportation, wrong storage and inexpert laying as well as of fixing contrary to regulations. Insulated lines and cables are especially susceptible to damage.

Information required for the selection of lines or cables

Table 21 Information required for the selection of lines or cables

Type of information required

Explanation

1. Amount of load current

Operating current

2. Amount of rated voltage

Low, medium or high voltage

3. Type of laying medium

Air, water, soil

4. Type of laying

Single laying, parallel laying, bunch laying

5. Place of laying

Indoors, outdoors and in soil, in waters, in swampy ground, in corrosion-developing environment, on bridges and with altitude differences

6. Ambient temperature

Average operating values

7. Mechanical stress, if any

Impact, shock, compression, tensile or bending stress

In any laying of lines or cables it is to be guaranteed that the lines and cables are fail-safe. This includes

- protection against mechanical damage, e.g. by covering caps, conduits,
- protection against earth displacement, constant vibrations,
- protection against chemical damage,
- protection against excessive heat.

Mechanical stress

The lines and cables must resist bending, tensile and compressive stress.

To resist frequent, varying bending stress, the conductor can be divided into several partial conductors of small cross section. Bandages and armouring are measures to resist compressive stress.

Thermal stress

- Temperature

The temperature of a conductor depends on the current density (measured in A/mm). the material and the possibility of heat dissipation.

- Lines in bunches

Because of poor heat dissipation, lines laid in bunches must not be operated with the maximum admissible rated load.

- Admissible heating

Excessive temperatures cause damage to the insulation (increased brittleness, shrinkage effects and charring, considerably reduced dielectric strength) which may result in breakdown with total failure of the line or cable.

Laying temperatures

The laying temperature must not be less than the specified minimum temperature of +4 C because the cable insulation and sheathing material will get brittle at low temperatures. When the temperature of the cables to be laid is less than + 4°C, the cables must be warmed up in a 20°C to 25°C warm room, such as a preheating tent, for about 36 to 48 hours, depending on the cable length. The cables may also be preheated by resistance heating of the cores by means of a transformer suitable for this purpose. But the limiting temperature of the conductor must not be exceeded with any heating method.

4.8.2. Laying of lines

General

For fixed laying of lines (solid system of laying), types of lines intended for that purpose are to be used only.

The relevant type of line is to be selected depending on the place of laying.

Places of laying:

- dry and sometimes damp rooms,
- damp or wet rooms or outdoors,
- in soil,
- in water,
- flush or buried,
- on the surface, on trays and supporting brackets,
- on wood, cardboard, particle board, fibre board,
- with the possibility of direct contact of the line.

Laying problems

Lines, whether flush, buried or on the surface, are to be protected against mechanical damage not only during laying but especially under service conditions. Invisible lines should be laid vertically or horizontally to facilitate tracking of their course.

Mechanical protection

Uncovered lines, e.g. moisture-proof lines, must be protected by conduits at any points where mechanical damage may occur (breakthroughs in walls, ceilings/floors).

Heat accumulation

With the methods of laying in common use today, such as on trays, supporting brackets, in ducts and conduits, the lines are laid in bunches. In each line bunch (single or multi-wire) and in each closed duct, heat may accumulate. In order to prevent accumulation of heat, the current load factor for the respective type of laying is to be taken into consideration in the selection of the line cross sections.

4.8.3. Laying of cables

Bending radii

In cable laying, when drawing off the cable from the cable drum and laying out the cable, e.g. with cable loops and cable connections the admissible bending radii are to be observed.

Table 22 Bending radii for power cables

Type of sheathing

Laying Position

Minimum bending radius

Lead and aluminium sheathing

during laying or bending
final position

20 d
15 d

Plain aluminium sheathing

during laying or bending
final position

25 d
20 d

Plastic sheathing

during laying or bending
final position

15 d
10 d

Laying in soil

Laying of cables in the soil depends on the various different local conditions.

Table 23 Minimum laying depth with and without cable cover

Rated voltage

Type of cable

Dimensions Built-up ground with cover

Ground not built-up with cover

without cover


-

m

m

m

up to 1000 V

with concentric conductor or metal sheathing

0.45(1)

0.7(1)

without concentric conductor or without metal sheathing

0.45

0.7

1.0

more than 1 kV

Compound-impregnated and plastic-insulated cables Oil-filled cables

0.7 1.0

(1) Instead of the cover, warning tape is to be preferably used.

The minimum laying depth refers to the bottom edge of the top cable in one cable route. Laying depths of less than 0.7 m in public traffic areas are subject to the approval of the respective local authority.

Cables in cable trenches are to be arranged on a 10 cm thick coat of sand. Moreover, the cable is to be covered by another 10 cm thick coat of sand after laying. The top coat of sand is then to be covered by the cable protecting cover. The following cable protecting covers are in use:

- Cable protecting caps

It is to be ensured that the cable protecting caps covering the cable are filled with sand. Any cavity between the cable and the cable ducts will result in accumulation of heat which largely reduces the load-carrying capacity.


Figure 46. Cable protecting cover with cable protecting caps - (1) correct application, (2) cavity between protecting cap and cable

- Brick covers

Brick covers are low-cost protecting covers and enable quick and easy covering.

- Concrete covers

Instead of bricks, concrete slabs may be used. They should be generally used for laying of oil-filled cables.


Figure 47. Cable protecting cover with concrete slabs and bricks - (1) with concrete slabs, (2) with bricks

- Cable conduits, moulded ducts

Cables run into buildings or under streets, rails and traffic-able ways require a high degree of mechanical protection. Conduits of clay, concrete or steel (not for single-conductor cables) are used for this purpose. If several cables are to be laid next to one another, moulded ducts are used.


Figure 48. Moulded duct

For the transition from the covering protection to the conduit it is to be made sure that the cable is not subjected to compressive or shearing stress.

- Cable layout in the soil

If several cables are laid in one cable trench, the lateral distance between the cables should be about 7 cm. Deviations are possible.

If high-voltage and low-voltage cables are laid in one cable trench, the high-voltage cables are to be laid deeper than the low-voltage cables.

Cable laying in the air

Cables should be circulated by air from all sides. Complete air circulation will not always be possible, e.g. in closed cable registers and laying of cables in ducts. In such cases a reduced load is to be calculated.

- Cable runs one upon the other High-voltage cables on the lower registers, low-voltage cables on the upper registers. Cables in ducts must not be laid on the bottom since the armouring would corrode in the event of intrusion of water. Cables intended for the protection, monitoring, control of plants or for transmission of information are to be laid separately from cables with rated voltages of more than 1 kV. Multi-conductor cables or cable systems with rated voltages of more than 1 kV should not be laid in layers one upon the other.

- Fixing of cables

Cables are to be fixed so as to prevent any deformation which is detrimental to the service properties. For cables on ceilings and walls it is also important to ensure good appearance.

Table 24 Distances for support and fixing of multi-conductor cables

Distances: in metres

Metal-sheathed cables

Plastic-insulated cables

Support horizontal

Fixing vertical

Support horizontal

Fixing vertical

<1

<3

<1

<1

=

=

=

=

- Distances

A minimum distance of 2 cm between the cables and between the cable and the wall is to be maintained to prevent accumulation of heat in service.

Laying in water

Laying of cables through inland waters (e.g. rivers, lakes and channels)

Cables in the open sea are laid by specialized companies by means of laying ships.

- Types of laying

· Laying on the bottom of stagnant waters.
· Laying in a dredged channel.
· Laying in conduits - only in brooks, ditches and rivulets.
· Setting of cables or cable conduits into the water bottom.

- Type of cable

The cable must have a strong armouring and good protection against corrosion. Plastic covering or double protective covering of impregnated fibrous material (AA) is suitable for this purpose.

4.8.4. Electric connections

General

Conductors must be connected to machines and appliances, i.e. they must have an electrically conductive connection. A connection between conductors is also necessary. The connection must enable reliable flow of current from one conductor to the other one. That means, there must be good contact between the conductors at the joint.


Figure 49. Types of contact - 1 point contact, 2 line contact, 3 surface contact

Type of connections (joints)

- Terminal connections:

· screw terminals,
· spring terminals,
· eccentric terminals,
· cone-type sleeve terminals.

- Plug-and-socket connections:

· appliance connectors,
· plug-in contacts.

- Wire-wrap connections.
- Soldered connections.
- Welded connections.
- Pressed connections.
- Sliding connections (sliding contacts).

Questions for recapitulation and testing

1. What are medium-voltage systems?
2. What is the difference between open and closed systems?
3. What is the purpose of network system coding to IEC 445?
4. What is the importance of the voltage in plant engineering?
5. What are the effects of the intensity of current to be transmitted on plant engineering?
6. What does the term “distributing plant” mean?
7. How can the change of length of busbars caused by heating be coped with?
8. What is the basic construction of a line?
9. What is the basic construction of a cable?
10. What is the advantage of a standard system of modular vessels for electrical engineering?
11. What types of switching and distributing plants do you know?
12. What is the purpose of switches?
13. What materials are insulators made of?
14. What is generally to be taken into account in laying of lines and cables?
15. What is to be ensured in cable laying with cable protecting caps?
16. What is the purpose of electric connections?

TO PREVIOUS SECTION OF BOOK TO NEXT SECTION OF BOOK